Error codes and trouble-shooting 

 

ƒ

Error codes:  

 

ƒ

Troubleshooting:

Symptom

Probable cause

Possible solution

The dehumidifer will 

not switch on

Circuit breaker(s) or fuse tripped 

Identify the reason for the fault, correct it 

and reset the circuit breaker or replace the 

fuse

On/ Off button set to off

Switch the machine on

Loose electrical connection

Verify that the remote installed control pad 

cable and the power cable are correctly 

tightened

In heating mode, the 

air is circulating but 

the air temperature 

at the inlet is the 

same as the air 

temperature at the 

outlet

T°C set point set to a temperature lower 

than the ambient T°C 

Modify the set point

3 minute time delay

Wait at least 5 minutes for the heating 

element to reach temperature

Bad contact

Check that the heating element connections 

are correctly tightened

If the problem is not resolved, contact the Procopi agent

Code

Meaning

Safety measure triggered

E1 

Faulty ambient air T° sensor (sensor or connection cable)

Shuts down the machine

E2 

Faulty defrosting sensor (sensor or connection cable)

The machine continues to run

E3 

Faulty humidity sensor (sensor or connection cable)

Shuts down the machine

EF 

Faulty exhaust air T° sensor (sensor or connection cable)

Turns off the heating element

EH 

Refrigerant T° sensor at the evaporator inlet is faulty (sensor or 

connection cable)

The machine continues to run

E4 

HP safety mechanism tripped

Stops the compressor

E5 

LP safety mechanism tripped

Stops the compressor

E7 

Exhaust air thermal protection tripped 

Turns off the heating element

EE 

Communication error

Shuts down the machine

EC 

Heating element thermal protection tripped 

Turns off the heating element

Содержание DH-120

Страница 1: ... 28 2015 12 Indice de révision B Code 33491 FR Page 1 GB Page 13 DESHUMIDIFIER CONSOLES Models DH 60 DH 90 DH 120 INSTALLATION AND OPERATING INSTRUCTIONS to be read carefully and kept for future reference ...

Страница 2: ...art up 22 Selection of the operating mode 22 Setting the humidity set point 22 Setting the temperature set point if the heating option is installed and active 23 Programming a postponed start and a postponed stop 23 Selecting the fan operating speed 24 Automatic defrosting 24 Shutting down the device 24 Locking unlocking the control pad 24 Verifying and setting and the operating parameters 24 INST...

Страница 3: ...h a breaking current rated for the amperage of the device must be installed at the head of the line We strongly recommend installation of a 30mA trip current residual current device upstream from their power supply Have the device wired in by a qualified professional At least once a year check that electrical wire contacts are correctly tightened Check regularly that the power cable is in good con...

Страница 4: ...ator Upon contact with the evaporator the air temperature falls until it reaches the condensation point of water vapour which causes the water to condense in fine droplets At the same time the heat transfer fluid recovers the calories given up by the ambient air Step 2 the fluid enters the compressor where it experiences a high increase in pressure and an increase in temperature Step 3 the cold de...

Страница 5: ...ta DH60 DH90 DH120 Dehumidification capacity 1 litres 24h 60 93 120 Nominal input power dehumidification mode W 990 1690 2000 Maximum input power dehumidification mode W 1200 2000 2450 Heating power output in dehumidification mode 2 W 2200 4200 5500 Power of the auxiliary heating element option W 2000 3000 3000 Air flow rate fan at full speed m3 h 800 1000 1200 Power supply monophasé 230 V 50Hz No...

Страница 6: ...ffect when selecting the installation site If the machine is free standing it must be set on solid stable and horizontal surface The dehumidifier is delivered with 4 height adjustable vibration damping pads to be screwed into place beneath the machine A flexible translucent condensate drainage tube length 2 m is also supplied This should be connected to the machine under the power cable connection...

Страница 7: ... length of the cable will not exceed 10 m If the cable in longer than 10 m use an extension cable with strands that have a wider cross section Solder the wires together use heat shrink tubing to insulate the soldered connections The power cable must be connected to a thermal magnetic protection device or a fuse holder fuse rated fro the machine s power consumption We strongly recommend that the ma...

Страница 8: ...elative humidity that should not be exceeded in the room the allowed range is between 30 and 99 Note that the dehumidifier cannot increase the relative humidity in the room if it falls below the set point To display the current set point value on screen press one of the arrow keys or once While the set point flashes on screen use the arrow keys and to increase or decrease this value in increments ...

Страница 9: ...ed while the machine is running Press the button Using the arrow keys or select a shut down delay of between 1 and 12 hours maximum one hour increments Allow the screen to return to the default display The OFF symbol appears in the bottom of the screen confirming that the OFF operation has been registered and that the machine will shut down after the programmed delay A delayed start can only be pr...

Страница 10: ...eratures below 10 C Shutting down the device Press the On Off button The compressor will stop approximately 30 seconds later the fan will also stop Nota bene There is a minimum time delay before the fan and compressor can be restarted approximately 30 seconds for the fan and approximately 2 minutes for the compressor Locking unlocking the key pad To deactivate the key pad press the two arrow keys ...

Страница 11: ...Fan operation once the set point is reached 0 the fan stops at the set point 1 the fan switches to low speed at the set point 1 9 C9 Exhaust air temperature 20 C 99 C Measured value 10 CA Refrigerant temperature at the evaporator inlet 20 C 99 C Measured value 11 Cb EXV step no 100 500P Measured value 12 CC Overheating target value Between 20 C and 20 C 5 C Stop the machine and cut the power suppl...

Страница 12: ...ector block over the one already in place Connect the neutral lug to the rear neutral pin on the white terminal First remove the neutral double lug already in place Connect the neutral cable of the heating element to the rear pin then reconnect the double lug to the front pin using one of the two lugs 7 Connect the female live lug to the free male lug of one of the two black components 8 Put the l...

Страница 13: ...ever spray the machine with a water jet Check regularly that the power cable connections heating element connections if this option is installed and the connections inside the electrical box are correctly tightened Check regularly that the air intake filter located behind the air intake grate at the bottom of the front casing is clean If necessary clean it with a cloth or soft bristle brush ...

Страница 14: ...ing element to reach temperature Bad contact Check that the heating element connections are correctly tightened If the problem is not resolved contact the Procopi agent Code Meaning Safety measure triggered E1 Faulty ambient air T sensor sensor or connection cable Shuts down the machine E2 Faulty defrosting sensor sensor or connection cable The machine continues to run E3 Faulty humidity sensor se...

Отзывы: