To modify the value of the parameter displayed, press the SET key. The value of the parameter will begin 

to flash, use the arrow keys (

 and 

) to modify the parameter. Press the SET key to validate the modi-

fication.  

 Press    or   .

 

„

Installation of the heating element (option) 

The heating element should only be installed by a qualified professional

.  

Parameter 

code

Parameter title

Allowed values

Default value

1

C1

With or without heating

0 without / 1 with

0

2

C2

Heating element temperature

From -20°C to +99°C

Value measured

3

C3

Humidity compensation to calibrate 

the humidity sensor

 From -5%  to  +5%

0%

4

C4

Minimum time lapse between two 

defrosting cycles

From 15Min to 90Min

20Min

5

C5

Defrosting cycle start temperature

From -10°C to 10°C

-1°C

6

C6

Defrosting cycle end temperature

From 0°C to 15°C

8°C

7

C7

Maximum duration of the defrosting 

cycle

From 2Min to 12Min

8Min

8

C8

Fan operation once the set point is 

reached

0 the fan stops at the set point  

/ 1 the fan switches to low speed at 

the set point

1

9

C9

Exhaust air temperature

-20°C~99°C

Measured value

10

CA

Refrigerant temperature at the 

evaporator inlet

-20°C~99°C

Measured value

11

Cb

EXV step no.

100~500P

Measured value

12

CC

Overheating target value

Between -20°C and +20°C

5°C

Stop the machine and cut the power supply to the dehumidifier.

1. 

Remove the plastic casing: extract the 2 Phillips head screws located 

midway up each side, and the 3 Phillips head screws on the bottom of 

the machine on each side. Also, to facilitate removal,  take the metallic 

strip off the back of the machine. Free the casing by pulling it forward. 

2. 

Place  the  element  flat  over  the  fins  and 

tube condenser with the black grating 

facing upwards and the connections 

oriented towards the electrical box. Feed 

the electrical wires through the opening 

located on the right hand side. 

 

Align the holes in the heating element plate 

with those of the base and insert the 4 

screws to attach the heating element 

to the machine. 

3. 

Open the lid of the electrical box 

Содержание DH-120

Страница 1: ... 28 2015 12 Indice de révision B Code 33491 FR Page 1 GB Page 13 DESHUMIDIFIER CONSOLES Models DH 60 DH 90 DH 120 INSTALLATION AND OPERATING INSTRUCTIONS to be read carefully and kept for future reference ...

Страница 2: ...art up 22 Selection of the operating mode 22 Setting the humidity set point 22 Setting the temperature set point if the heating option is installed and active 23 Programming a postponed start and a postponed stop 23 Selecting the fan operating speed 24 Automatic defrosting 24 Shutting down the device 24 Locking unlocking the control pad 24 Verifying and setting and the operating parameters 24 INST...

Страница 3: ...h a breaking current rated for the amperage of the device must be installed at the head of the line We strongly recommend installation of a 30mA trip current residual current device upstream from their power supply Have the device wired in by a qualified professional At least once a year check that electrical wire contacts are correctly tightened Check regularly that the power cable is in good con...

Страница 4: ...ator Upon contact with the evaporator the air temperature falls until it reaches the condensation point of water vapour which causes the water to condense in fine droplets At the same time the heat transfer fluid recovers the calories given up by the ambient air Step 2 the fluid enters the compressor where it experiences a high increase in pressure and an increase in temperature Step 3 the cold de...

Страница 5: ...ta DH60 DH90 DH120 Dehumidification capacity 1 litres 24h 60 93 120 Nominal input power dehumidification mode W 990 1690 2000 Maximum input power dehumidification mode W 1200 2000 2450 Heating power output in dehumidification mode 2 W 2200 4200 5500 Power of the auxiliary heating element option W 2000 3000 3000 Air flow rate fan at full speed m3 h 800 1000 1200 Power supply monophasé 230 V 50Hz No...

Страница 6: ...ffect when selecting the installation site If the machine is free standing it must be set on solid stable and horizontal surface The dehumidifier is delivered with 4 height adjustable vibration damping pads to be screwed into place beneath the machine A flexible translucent condensate drainage tube length 2 m is also supplied This should be connected to the machine under the power cable connection...

Страница 7: ... length of the cable will not exceed 10 m If the cable in longer than 10 m use an extension cable with strands that have a wider cross section Solder the wires together use heat shrink tubing to insulate the soldered connections The power cable must be connected to a thermal magnetic protection device or a fuse holder fuse rated fro the machine s power consumption We strongly recommend that the ma...

Страница 8: ...elative humidity that should not be exceeded in the room the allowed range is between 30 and 99 Note that the dehumidifier cannot increase the relative humidity in the room if it falls below the set point To display the current set point value on screen press one of the arrow keys or once While the set point flashes on screen use the arrow keys and to increase or decrease this value in increments ...

Страница 9: ...ed while the machine is running Press the button Using the arrow keys or select a shut down delay of between 1 and 12 hours maximum one hour increments Allow the screen to return to the default display The OFF symbol appears in the bottom of the screen confirming that the OFF operation has been registered and that the machine will shut down after the programmed delay A delayed start can only be pr...

Страница 10: ...eratures below 10 C Shutting down the device Press the On Off button The compressor will stop approximately 30 seconds later the fan will also stop Nota bene There is a minimum time delay before the fan and compressor can be restarted approximately 30 seconds for the fan and approximately 2 minutes for the compressor Locking unlocking the key pad To deactivate the key pad press the two arrow keys ...

Страница 11: ...Fan operation once the set point is reached 0 the fan stops at the set point 1 the fan switches to low speed at the set point 1 9 C9 Exhaust air temperature 20 C 99 C Measured value 10 CA Refrigerant temperature at the evaporator inlet 20 C 99 C Measured value 11 Cb EXV step no 100 500P Measured value 12 CC Overheating target value Between 20 C and 20 C 5 C Stop the machine and cut the power suppl...

Страница 12: ...ector block over the one already in place Connect the neutral lug to the rear neutral pin on the white terminal First remove the neutral double lug already in place Connect the neutral cable of the heating element to the rear pin then reconnect the double lug to the front pin using one of the two lugs 7 Connect the female live lug to the free male lug of one of the two black components 8 Put the l...

Страница 13: ...ever spray the machine with a water jet Check regularly that the power cable connections heating element connections if this option is installed and the connections inside the electrical box are correctly tightened Check regularly that the air intake filter located behind the air intake grate at the bottom of the front casing is clean If necessary clean it with a cloth or soft bristle brush ...

Страница 14: ...ing element to reach temperature Bad contact Check that the heating element connections are correctly tightened If the problem is not resolved contact the Procopi agent Code Meaning Safety measure triggered E1 Faulty ambient air T sensor sensor or connection cable Shuts down the machine E2 Faulty defrosting sensor sensor or connection cable The machine continues to run E3 Faulty humidity sensor se...

Отзывы: