TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
42
repeat point 13 until the value that appears on the B4 display, regarding parameters
120, 121, 152, 153, corresponds to the one shown in the table:
PARAMETER
VALUE
120
50.0 + parameter offset value
121
-20.0 + parameter offset value
152
25.0 + parameter offset value
153
05.0 + parameter offset value
16. exit from the programming menu, press the NASCOSTO 2* + C3 keys, “arrow up”;
17. disconnect the power supply to the unit;
18. remove the self-calibration kit;
19. reconnect the power supply to the unit;
20. enter the programming menu (see point 9);
21. re-program the unit (check the value of the parameters by printing them, and set the
value of any new parameters). Scroll through the parameter list using the C3 keys. The
value of the parameter is visualised on the B5 display;
22. exit from the programming menu (see point 16);
23. disconnect the power supply to the unit;
24. reconnect the power supply to the unit;
25. enable the compressors (see chap.8.3).
(*)For information on these keys, contact the Climaveneta customer service dept.