TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
36
8.3 Alarm history printing
NASCOSTO 1+ T 6
The record printout has 7 columns and is structured as follows:
DESCRIPTION
LIMITS
1
Progressive print number
001-200
2
Hour of event
00-24
2b
Dd/mm/yy of event
3
Alarm code
000-299
4
Number of events in the indicated hour
1-32
5
Compressor or circuit number
1-8
6
29-character alphanumeric string for alarm
description and associated compressor and/or
circuit number to which the alarm refers
Example:
** ALARM HISTORY **
PROG
.
No.
HR DATE FREQ/
HR
CIRC
.
COMP
COD.
ALM.
DESCR.
ALM.
34 13 07/10/97
01
4
201 MAXIMUM PRESSURE
33 13 07/10/97
04
4
116 MAXIMUM PRESSURE
32 13 07/10/97
02
3
116 MAXIMUM PRESSURE
31 13 07/10/97
03
2
116 MAXIMUM PRESSURE
30 13 07/10/97
01
2
201 MAXIMUM PRESSURE
29 13 07/10/97
01
1
116 MAXIMUM PRESSURE
28 13 07/10/97
01
1
201 MAXIMUM PRESSURE
27 13 07/10/97
01
3
103 THERMAL PROTECTION
26 13 07/10/97
01
4
103 THERMAL PROTECTION
25 13 07/10/97
01
2
103 THERMAL PROTECTION
24 13 07/10/97
01
1
103 THERMAL PROTECTION
23 13 07/10/97
01
000 ANTIFREEZE
22 10 07/10/97
02
402 TEMPERATURE PROBE ERROR
21 10 07/10/97
02
401 TEMPERATURE PROBE ERROR
20 16 06/10/97
01
000 ANTIFREEZE
19 14 06/10/97
01
4
101 OIL DIFFERENTIAL
18 14 06/10/97
03
3
213 MINIMUM PRESSURE
17 13 06/10/97
03
3
213 MINIMUM PRESSURE
16 13 06/10/97
03
2
213 MINIMUM PRESSURE
15 13 06/10/97
02
1
213 MINIMUM PRESSURE
14 12 06/10/97
01
1
203 PUMP-DOWN PRESSURE
13 12 06/10/97
03
4
203 PUMP-DOWN PRESSURE
12 12 06/10/97
05
3
203 PUMP-DOWN PRESSURE
11 12 06/10/97
03
2
203 PUMP-DOWN PRESSURE
10 12 06/10/97
01
1
101 OIL DIFFERENTIAL
9
11 06/10/97
01
1
203 PUMP-DOWN PRESSURE
8
11 06/10/97
03
4
203 PUMP-DOWN PRESSURE
7
11 06/10/97
04
4
101 OIL DIFFERENTIAL
6
11 06/10/97
01
3
101 OIL DIFFERENTIAL
5
11 06/10/97
02
2
101 OIL DIFFERENTIAL
4
11 06/10/97
04
1
101 OIL DIFFERENTIAL
3
13 15/08/92
01
000 ANTIFREEZE
2
10 04/07/92
01
000 ANTIFREEZE
1
10 04/07/92
02
003 COLD FLOW SWITCH INLET