54
230
M
HOT WATER SET HIGHER LIMIT
-20
↔
100
50 °C
231
M
HOT WATER SET LOWER LIMIT
-20
↔
100
30 °C
232
M
COLD WATER SET HIGHER LIMIT
-20
↔
100
18 °C
233
M
COLD WATER SET LOWER LIMIT
-50
↔
100
5 °C
234
M
HOT WATER
∆
t HIGHER LIMIT
1
↔
50
5 °C
235
M
HOT WATER
∆
t LOWER LIMIT
1
↔
50
1 °C
236
M
COLD WATER
∆
t HIGHER LIMIT
1
↔
50
5 °C
237
M
COLD WATER
∆
t LOWER LIMIT
1
↔
50
1 °C
240
CI
TIME REMAINING TO CIRCUIT 1 END OF
DEFROST CYCLE
------------------
min
241
CI
TIME REMAINING TO CIRCUIT 2 END OF
DEFROST CYCLE
------------------
min
242
CI
TIME REMAINING TO CIRCUIT 3 END OF
DEFROST CYCLE
------------------
min
243
CI
TIME REMAINING TO CIRCUIT 4 END OF
DEFROST CYCLE
------------------
min
244
CI
TIME REMAINING TO CIRCUIT 5 END OF
DEFROST CYCLE
------------------
min
245
CI
TIME REMAINING TO CIRCUIT 6 END OF
DEFROST CYCLE
------------------
min
246
CI
TIME REMAINING TO CIRCUIT 7 END OF
DEFROST CYCLE
------------------
min
247
CI
TIME REMAINING TO CIRCUIT 8 END OF
DEFROST CYCLE
------------------
min
250
M
ENABLE SUBCOOLING
0
↔
1
0 flag
251
M
DELAY TIME TO START REGULATION
0
↔
120
60 sec
252
M
DELAY TIME TO ACTIVATION OF RELAY
0
↔
120
30 sec
253
M
SUBCOOLING SET POINT
0
↔
100
5.0 °C
254
M
SUBCOOLING PROPORTIONAL BAND
0
↔
10
1.0 °C
255
M
TYPE OF REFRIGERANT GAS USED
1
↔
3
Tab. 13-8
PARAMETER VALUE
DESCRIPTION
1
R 22
2
R 134a
3
R 407c
4
R 404a
Table 13-8 TYPE OF REFRIGERANT GAS
260
M
0: MODEM DISABLED
1: Enables unit to answer calls by modem
2: Enables the unit to answer and call by modem
0
↔
2
0 Num
261
M
Mask for machine alarms which activate the call
0
↔
0xFFF
0 Mask
262
M
Mask for circuit alarms which activate the call
0
↔
3F
0 Mask
263
M
Mask for compressor alarms which activate the call
0
↔
0F
0 Mask
264
M
Type of serial port listening prior to the transmission
of the initialisation command
0
↔
120
4 sec
265
M
Type of serial port listening prior to the transmission
of the connection command
0
↔
120
60 sec
266
M
Maximum number of call attempts to the same
number
0
↔
5
2 Num
267
M
Delay time between two successive attempts to call the
same number
0
↔
600
10 sec
268
M
Maximum wait time for reply after the initialisation
command
0
↔
120
2 sec
269
M
Maximum wait time for reply after the connection
command
0
↔
120
45 sec
270
M
ENABLE DATA LOGGER
(see note in chapter 8.10)
0
↔
1
1 flag