TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
31
7.1.1 Default set point settings
The following table shows, based on the number of steps, the commonly used set point
and
∆
t values.
The theoretical minimum and maximum values indicated in the table for the outlet
temperature refer to nominal flow rate operation, and therefore with a 5° C evaporator
thermal head.
No. of steps Set point [°C]
∆
∆
t [°C]
Theoret. min out temp. Theoret. max out temp.
1
11
1
6
12
2
9.5
2.5
5.7
10.8
3
8
4
5.6
9.4
>=4
7
5
<=5.7
<=8.3
Warning:
the regulation is made based on the temperature reading at the evaporator’s
inlet.