TECHNICAL DATA
a-LIFE3 / DLIO - DFIO
0104
0204
0304
0404
0504
ELECTRICAL DATA
Power supply
V/ph/Hz
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
4 PIPES SYSTEM CONFIGURATION
ENERGY EFFICIENCY
COOLING (EN14511 VALUE)
FCEER
(1)(6)
kW/kW
34
41
42
50
64
FCEER Class
E
E
E
E
D
HEATING ONLY (EN14511 VALUE)
FCCOP
(2)(6)
kW/kW
44
45
49
51
69
FCCOP Class
E
E
E
E
E
PERFORMANCE
MIN SPEED
Fan Power Input
(1)
W
20,0
20,0
25,0
25,0
26,0
Air flow rate
(1)
m³/h
186
197
239
252
346
Total capacity in cooling mode
(1)
kW
0,73
0,86
1,20
1,42
1,93
Total Net Cooling Capacity
(1)(6)(7)
kW
0,71
0,84
1,18
1,40
1,90
Sensible capacity in cooling mode
(1)
kW
0,62
0,69
1,02
1,14
1,46
Net sensible cooling capacity
(1)(6)(7)
kW
0,60
0,67
1,00
1,12
1,43
Net latent power in cooling
(1)(6)(7)
kW
0,11
0,17
0,18
0,28
0,47
Max water flow
(1)
l/s
0,03
0,04
0,06
0,07
0,09
Pressure Drop in cooling mode
(1)
kPa
0,5
4,6
1,6
8,4
4,0
Total capacity (heating mode)
(2)
kW
0,93
0,97
1,35
1,41
2,01
Total Net Heating Capacity
(2)(6)
kW
0,95
0,99
1,37
1,43
2,04
Water flow in heating mode
(2)
l/s
0,02
0,02
0,03
0,03
0,05
Pressure drop in heating mode
(2)
kPa
4,1
4,4
5,1
5,5
9,2
Sound Pressure
(3)
dB(A)
29
29
33
33
33
Sound Power
(4)(7)
dB(A)
38
38
42
42
42
MED SPEED
Fan Power Input
(1)
W
31,0
31,0
43,0
43,0
46,0
Air flow rate
(1)
m³/h
261
276
365
385
509
Total capacity in cooling mode
(1)
kW
1,11
1,31
1,69
2,03
2,69
Total Net Cooling Capacity
(1)(6)(7)
kW
1,08
1,28
1,65
1,99
2,65
Sensible capacity in cooling mode
(1)
kW
0,96
1,06
1,49
1,65
2,10
Net sensible cooling capacity
(1)(6)(7)
kW
0,93
1,03
1,45
1,61
2,05
Net latent power in cooling
(1)(6)(7)
kW
0,15
0,25
0,20
0,38
0,59
Max water flow
(1)
l/s
0,05
0,06
0,08
0,10
0,13
Pressure Drop in cooling mode
(1)
kPa
0,9
9,7
2,9
14,7
7,2
Total capacity (heating mode)
(2)
kW
1,21
1,24
1,85
1,93
2,70
Total Net Heating Capacity
(2)(6)
kW
1,24
1,27
1,89
1,97
2,75
Water flow in heating mode
(2)
l/s
0,03
0,03
0,04
0,05
0,07
Pressure drop in heating mode
(2)
kPa
6,3
6,5
8,6
9,3
15,0
Sound Pressure
(3)
dB(A)
38
39
42
43
41
Sound Power
(4)(7)
dB(A)
47
48
51
52
50
MAX SPEED
Fan Power Input
(1)
W
49,0
49,0
66,0
66,0
71,0
Air flow rate
(1)
m³/h
368
389
472
498
676
Total capacity in cooling mode
(1)
kW
1,41
1,65
2,11
2,48
3,27
Total Net Cooling Capacity
(1)(6)(7)
kW
1,36
1,60
2,04
2,42
3,20
Sensible capacity in cooling mode
(1)
kW
1,27
1,43
1,83
2,07
2,58
Net sensible cooling capacity
(1)(6)(7)
kW
1,22
1,38
1,76
2,00
2,51
Net latent power in cooling
(1)(6)(7)
kW
0,14
0,22
0,28
0,41
0,69
Max water flow
(1)
l/s
0,07
0,08
0,10
0,12
0,16
Pressure Drop in cooling mode
(1)
kPa
1,2
14,5
4,2
20,2
10,2
Total capacity (heating mode)
(2)
kW
1,55
1,60
2,23
2,33
3,33
Total Net Heating Capacity
(2)(6)
kW
1,60
1,65
2,30
2,40
3,40
Water flow in heating mode
(2)
l/s
0,04
0,04
0,05
0,06
0,08
Pressure drop in heating mode
(2)
kPa
9,4
9,9
11,8
12,7
21,2
Sound Pressure
(3)
dB(A)
45
46
48
49
48
Sound Power
(4)(7)
dB(A)
54
55
57
58
57
SIZE AND WEIGHT
A
(5)
mm
545
545
745
745
945
B
(5)
mm
215
215
215
215
215
H
(5)
mm
450
450
450
450
450
Operating weight
(5)
kg
12
13
15
16
21
Notes:
1 Room temperature 27°C d.b./18,9°C w.b., Chilled water (in/out) 7°C/12°C.
2 Room temperature 20 °C d.b., hot water (in/out) 65/55 °C
3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.
4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
6 Values in compliance with EN14511-3:2013.
7 Values in compliance with [REGULATION (EU) N. 2016/2281]
Certified data in EUROVENT
10