TECHNICAL DATA
i-LIFE2 / DLIV-DFIV
0204
0404
0604
0804
1004
ELECTRICAL DATA
Power supply
V/ph/Hz
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
4 PIPES SYSTEM CONFIGURATION
ENERGY EFFICIENCY
COOLING (EN14511 VALUE)
FCEER
(1)(6)
kW/kW
125
122
124
120
136
FCEER Class
B
B
B
B
B
HEATING ONLY (EN14511 VALUE)
FCCOP
(2)(6)
kW/kW
104
99
110
103
116
FCCOP Class
C
D
C
C
C
PERFORMANCE
MIN SPEED
Fan Power Input
(1)
W
7,00
7,86
6,95
7,57
14,2
Air flow rate
(1)
m³/h
176
241
289
318
536
Total capacity in cooling mode
(1)
kW
0,93
1,50
1,95
2,25
3,23
Total Net Cooling Capacity
(1)(6)(7)
kW
0,92
1,49
1,95
2,24
3,22
Sensible capacity in cooling mode
(1)
kW
0,73
1,16
1,50
1,69
2,43
Net sensible cooling capacity
(1)(6)(7)
kW
0,72
1,16
1,49
1,69
2,42
Net latent power in cooling
(1)(6)(7)
kW
0,20
0,34
0,45
0,56
0,80
Max water flow
(1)
l/s
0,04
0,07
0,09
0,11
0,15
Pressure Drop in cooling mode
(1)
kPa
3
7
3
4
9
Total capacity (heating mode)
(2)
kW
0,74
1,08
1,53
1,77
2,42
Total Net Heating Capacity
(2)(6)
kW
0,75
1,09
1,54
1,77
2,43
Water flow in heating mode
(2)
l/s
0,02
0,03
0,04
0,04
0,06
Pressure drop in heating mode
(2)
kPa
2
3
6
3
13
Sound Pressure
(3)
dB(A)
30
33
33
34
37
Sound Power
(4)(7)
dB(A)
40
42
42
43
46
MED SPEED
Fan Power Input
(1)
W
10,9
15,4
15,0
24,1
43,0
Air flow rate
(1)
m³/h
262
377
548
756
917
Total capacity in cooling mode
(1)
kW
1,35
2,29
3,01
4,30
5,38
Total Net Cooling Capacity
(1)(6)(7)
kW
1,34
2,28
3,00
4,28
5,34
Sensible capacity in cooling mode
(1)
kW
1,06
1,74
2,39
3,17
4,13
Net sensible cooling capacity
(1)(6)(7)
kW
1,05
1,72
2,37
3,15
4,09
Net latent power in cooling
(1)(6)(7)
kW
0,29
0,56
0,63
1,13
1,26
Max water flow
(1)
l/s
0,06
0,11
0,14
0,21
0,26
Pressure Drop in cooling mode
(1)
kPa
6
16
8
15
24
Total capacity (heating mode)
(2)
kW
1,07
1,66
2,35
3,37
4,03
Total Net Heating Capacity
(2)(6)
kW
1,08
1,67
2,36
3,40
4,07
Water flow in heating mode
(2)
l/s
0,03
0,04
0,06
0,08
0,10
Pressure drop in heating mode
(2)
kPa
5
7
14
9
34
Sound Pressure
(3)
dB(A)
38
42
44
45
46
Sound Power
(4)(7)
dB(A)
47
51
53
54
56
MAX SPEED
Fan Power Input
(1)
W
19,8
42,9
36,0
45,3
112
Air flow rate
(1)
m³/h
363
585
808
976
1352
Total capacity in cooling mode
(1)
kW
1,82
3,38
4,36
5,45
7,50
Total Net Cooling Capacity
(1)(6)(7)
kW
1,80
3,34
4,33
5,41
7,39
Sensible capacity in cooling mode
(1)
kW
1,44
2,59
3,49
4,04
5,81
Net sensible cooling capacity
(1)(6)(7)
kW
1,42
2,55
3,46
3,99
5,70
Net latent power in cooling
(1)(6)(7)
kW
0,38
0,78
0,87
1,41
1,69
Max water flow
(1)
l/s
0,09
0,16
0,21
0,26
0,36
Pressure Drop in cooling mode
(1)
kPa
10
34
17
25
47
Total capacity (heating mode)
(2)
kW
1,48
2,44
3,41
4,27
5,62
Total Net Heating Capacity
(2)(6)
kW
1,50
2,48
3,45
4,31
5,73
Water flow in heating mode
(2)
l/s
0,04
0,06
0,08
0,10
0,14
Pressure drop in heating mode
(2)
kPa
9
15
28
14
63
Sound Pressure
(3)
dB(A)
48
51
53
54
56
Sound Power
(4)(7)
dB(A)
57
60
62
63
65
SIZE AND WEIGHT
A
(5)
mm
450
650
850
1050
1250
B
(5)
mm
215
215
215
215
215
H
(5)
mm
450
450
450
450
450
Operating weight
(5)
kg
12
15
22
26
30
Notes:
1 Room temperature 27°C d.b./18,9°C w.b., Chilled water (in/out) 7°C/12°C.
2 Room temperature 20 °C d.b., hot water (in/out) 65/55 °C
3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.
4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
6 Values in compliance with EN14511-3:2013.
7 Values in compliance with [REGULATION (UE) N.2016/2281]
Certified data in EUROVENT