14
EN
TECHNICAL DATA
a-LIFE3 / DLIO - DFIO
0604
0704
0804
0904
1004
ELECTRICAL DATA
Power supply
V/ph/Hz
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
4 PIPES SYSTEM CONFIGURATION
ENERGY EFFICIENCY
COOLING (EN14511 VALUE)
FCEER
(1)(6)
kW/kW
74
52
57
50
54
FCEER Class
D
E
D
E
E
HEATING ONLY (EN14511 VALUE)
FCCOP
(2)(6)
kW/kW
73
49
51
49
50
FCCOP Class
D
E
E
E
E
PERFORMANCE
MIN SPEED
Fan Power Input
(1)
W
26,0
48,0
48,0
61,0
61,0
Air flow rate
(1)
m³/h
365
477
504
537
567
Total capacity in cooling mode
(1)
kW
2,23
2,95
3,21
3,43
3,69
Total Net Cooling Capacity
(1)(6)(7)
kW
2,21
2,90
3,16
3,37
3,63
Sensible capacity in cooling mode
(1)
kW
1,65
2,44
2,58
2,70
2,96
Net sensible cooling capacity
(1)(6)(7)
kW
1,62
2,39
2,53
2,64
2,90
Net latent power in cooling
(1)(6)(7)
kW
0,58
0,51
0,63
0,73
0,73
Max water flow
(1)
l/s
0,11
0,14
0,15
0,16
0,18
Pressure Drop in cooling mode
(1)
kPa
4,7
10,7
7,3
15,0
12,2
Total capacity (heating mode)
(2)
kW
2,13
2,64
2,76
3,18
3,29
Total Net Heating Capacity
(2)(6)
kW
2,16
2,69
2,81
3,24
3,35
Water flow in heating mode
(2)
l/s
0,05
0,06
0,07
0,08
0,08
Pressure drop in heating mode
(2)
kPa
10,1
3,9
4,2
4,9
2,7
Sound Pressure
(3)
dB(A)
33
39
39
39
39
Sound Power
(4)(7)
dB(A)
42
48
48
48
48
MED SPEED
Fan Power Input
(1)
W
46,0
86,0
86,0
105
105
Air flow rate
(1)
m³/h
538
720
760
851
899
Total capacity in cooling mode
(1)
kW
3,10
4,03
4,49
5,02
5,37
Total Net Cooling Capacity
(1)(6)(7)
kW
3,06
3,95
4,41
4,92
5,27
Sensible capacity in cooling mode
(1)
kW
2,42
3,37
3,72
4,21
4,43
Net sensible cooling capacity
(1)(6)(7)
kW
2,37
3,28
3,63
4,11
4,32
Net latent power in cooling
(1)(6)(7)
kW
0,68
0,66
0,77
0,81
0,94
Max water flow
(1)
l/s
0,15
0,19
0,21
0,24
0,26
Pressure Drop in cooling mode
(1)
kPa
8,5
18,5
13,2
29,2
24,2
Total capacity (heating mode)
(2)
kW
2,86
3,59
3,75
4,50
4,66
Total Net Heating Capacity
(2)(6)
kW
2,91
3,68
3,84
4,61
4,76
Water flow in heating mode
(2)
l/s
0,07
0,09
0,09
0,11
0,11
Pressure drop in heating mode
(2)
kPa
16,5
6,5
7,0
8,8
4,9
Sound Pressure
(3)
dB(A)
41
47
47
49
50
Sound Power
(4)(7)
dB(A)
50
56
56
58
59
MAX SPEED
Fan Power Input
(1)
W
71,0
130
130
146
146
Air flow rate
(1)
m³/h
713
966
1019
1104
1166
Total capacity in cooling mode
(1)
kW
3,77
4,78
5,33
5,97
6,45
Total Net Cooling Capacity
(1)(6)(7)
kW
3,70
4,65
5,20
5,83
6,31
Sensible capacity in cooling mode
(1)
kW
2,97
4,08
4,53
5,07
5,39
Net sensible cooling capacity
(1)(6)(7)
kW
2,90
3,95
4,40
4,92
5,24
Net latent power in cooling
(1)(6)(7)
kW
0,80
0,70
0,80
0,90
1,06
Max water flow
(1)
l/s
0,18
0,23
0,25
0,29
0,31
Pressure Drop in cooling mode
(1)
kPa
12,0
25,0
17,8
39,6
33,7
Total capacity (heating mode)
(2)
kW
3,53
4,47
4,67
5,45
5,65
Total Net Heating Capacity
(2)(6)
kW
3,60
4,60
4,80
5,60
5,80
Water flow in heating mode
(2)
l/s
0,09
0,11
0,11
0,13
0,14
Pressure drop in heating mode
(2)
kPa
23,4
9,4
10,1
12,1
6,8
Sound Pressure
(3)
dB(A)
49
53
54
55
56
Sound Power
(4)(7)
dB(A)
58
62
63
64
65
SIZE AND WEIGHT
A
(5)
mm
945
1145
1145
1345
1345
B
(5)
mm
215
215
215
215
215
H
(5)
mm
450
450
450
450
450
Operating weight
(5)
kg
22
25
26
29
30
Notes:
1 Room temperature 27°C d.b./18,9°C w.b., Chilled water (in/out) 7°C/12°C.
2 Room temperature 20 °C d.b., hot water (in/out) 65/55 °C
3 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground. Non -binding value obtained fron sound power level.
4 Sound power on the basis of measurements made in compliance with ISO 3741 and Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
6 Values in compliance with EN14511-3:2013.
7 Values in compliance with [REGULATION (EU) N. 2016/2281]
Certified data in EUROVENT
11