C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54.4ºC]
85ºF [29ºC]
Min. entering air, DB/WB
50/45ºF [10/7ºC]
40ºF [4.5ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
110/83ºF [43/28ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
Commissioning Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where
humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water
temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other
two factors should be at normal levels to ensure proper unit operation. Extreme variations in temperature and humidity
and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table 6a for
operating limits.
Unit Starting and Operating Conditions
Table 9b: Building Commissioning Limits
Commissioning Conditions
Starting conditions vary depending upon model and are based upon the following notes:
Notes:
1. Conditions in Table 6b are not normal or continuous operating conditions. Minimum/maximum limits are start-up
conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under these
conditions on a regular basis.
2. Voltage utilization range complies with AHRI Standard 110.
Table 9a: Operating Limits
Cooling
Heating
Cooling
Heating
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54.4ºC]
85ºF [29ºC]
130ºF [54.4ºC]
85ºF [29ºC]
130ºF [54.4ºC]
85ºF [29ºC]
Min. entering air, DB/WB
*
60/45ºF [16/7ºC]
40ºF [4.4ºC]
*60/50ºF [16/10ºC]
45ºF [7ºC]
*65/50ºF [18/10ºC]
45ºF [7.2ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
100/75ºF [38/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-6.7ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
TC
TS
TT
Operating Limits
Normal Water Flow
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
*If with ClimaDry
®
70/61ºF (21/16ºC)
*If with ClimaDry
®
65/55ºF (18/13ºC)
Cooling
Heating
Cooling
Heating
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
Min. entering air, DB/WB
70/60ºF [21/16ºC]
60ºF [15.6ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-7ºC]
30ºF [-1ºC]
20ºF [-7ºC]
50ºF [10ºC]
50ºF [10ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
60-90ºF [15 to 32ºC] 60-70ºF [15 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
110ºF [43ºC]
90ºF [32ºC]
TC
GR
GS
Operating Limits
Normal Water Flow
[2.7 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
2.5 to 3.0 gpm / ton
Cooling
Heating
Cooling
Heating
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54.4ºC]
85ºF [29ºC]
130ºF [54.4ºC]
85ºF [29ºC]
130ºF [54.4ºC]
85ºF [29ºC]
Min. entering air, DB/WB
*
60/45ºF [16/7ºC]
40ºF [4.4ºC]
*60/50ºF [16/10ºC]
45ºF [7ºC]
*65/50ºF [18/10ºC]
45ºF [7.2ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
100/75ºF [38/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-6.7ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
TC
TS
TT
Operating Limits
Normal Water Flow
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
*If with ClimaDry
®
70/61ºF (21/16ºC)
*If with ClimaDry
®
65/55ºF (18/13ºC)
Cooling
Heating
Cooling
Heating
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
Min. entering air, DB/WB
70/60ºF [21/16ºC]
60ºF [15.6ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-7ºC]
30ºF [-1ºC]
20ºF [-7ºC]
50ºF [10ºC]
50ºF [10ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
60-90ºF [15 to 32ºC] 60-70ºF [15 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
110ºF [43ºC]
90ºF [32ºC]
TC
GR
GS
Operating Limits
Normal Water Flow
[2.7 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
2.5 to 3.0 gpm / ton