44
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Blower Performance Data – TR060
All TR units with optional CV-ECM fan motor automatically adjusts for the reheat coil. The small
additional pressure drop of the reheat coil causes the CV-ECM motor to slightly increase RPM to
overcome the added pressure drop, and maintain selected CFM up to the maximum ESP.
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1950
1500
PSC
Low
CFM
1803
1774
1744
1695
1637
1568
Medium
CFM
1999
1950
1901
1852
1793
1744
1676
1588
High
CFM
1881
1815
1710
1596
1416
1216
1216
1950
1500
PSC -
High
Static
Low
CFM
1882
1872
1852
1842
1813
1793
1764
1715
1666
1588
Medium
CFM
2107
2097
2038
1999
1980
1940
1891
1842
1460
1715
High
CFM
2342
2323
2293
2254
2195
2156
2087
2019
1940
1852
1950
1500
ECM -
Constant
Torque
1
RPM
768
797
830
863
Power (W)
342
354
366
380
CFM
1685
1640
1593
1545
2
RPM
836
867
895
922
955
989
1020
1048
1081
Power (W)
460
476
489
501
518
533
548
561
577
CFM
1879
1833
1795
1754
1705
1657
1608
1563
1514
3
RPM
923
953
974
1000
1025
1052
1079
1109
1137
Power (W)
648
666
678
694
708
724
740
757
773
CFM
2113
2069
2039
1998
1963
1925
1885
1840
1795
4
RPM
972
994
1020
1041
1066
1090
1114
1144
1170
Power (W)
771
785
803
817
832
848
864
883
900
CFM
2235
2198
2163
2130
2094
2061
2019
1977
1939
5
RPM
1003
1025
1050
1074
1099
1122
1147
1166
1194
1209
Power (W)
866
881
899
916
934
951
970
977
973
969
CFM
2322
2290
2253
2219
2188
2152
2120
2083
2013
1940
1950
1500
ECM -
Constant
Volume
Minimum CFM
RPM
705
773
836
894
949
998
1044
1085
1121
1153
Power (W)
246
301
354
405
453
500
544
587
627
665
CFM
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
Default CFM
RPM
852
899
949
992
1031
1085
1136
1179
1225
1272
Power (W)
501
562
629
683
731
804
871
926
986
1047
CFM
1950
1950
1950
1950
1950
1950
1950
1950
1950
1950
Maximum CFM
RPM
995
1020
1044
1069
1094
Power (W)
885
896
901
916
937
CFM
2200
2200
2200
2200
2200
See ECM control section for details on setting airflow.
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidification mode if HP CFM is on setting 1.
ClimaDry is factory wired to operate in stage 2 airflow.
Black areas denote ESP where operation is not recommended.
PSC: Units factory shipped on medium speed. Other speeds require field selection.
CT ECM: Units factory shipped on Speed Tap 2 for Fan-Only and Speed Tap 3 for Heating/Cooling.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply. Performance may vary as the power supply varies from the rated.
All data is shown wet coil with clean 1” filter.
All data is ran at 80 °F DB and 67 °F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.