C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Blower Performance Data – TR030
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1000
750
PSC
Low
CFM
1017
979
931
884
827
751
Medium
CFM
1140
1093
1036
988
922
846
High
CFM
1102
1045
979
903
798
1000
750
PSC -
High
Static
Low
CFM
979
941
912
865
798
Medium
CFM
1074
979
884
779
High
CFM
1102
988
874
760
1000
750
ECM -
Constant
Torque
1
RPM
880
925
994
1049
1101
Power (W)
158
165
176
184
192
CFM
904
873
832
796
763
2
RPM
956
998
1038
1105
1156
1203
1248
1295
1344
Power (W)
211
219
227
240
250
258
267
276
285
CFM
1020
992
965
927
894
864
835
805
771
3
RPM
1034
1072
1110
1145
1209
1250
1303
1346
1387
1422
Power (W)
280
289
298
306
321
330
342
351
361
368
CFM
1139
1113
1089
1064
1027
999
966
937
910
879
4
RPM
1095
1130
1166
1201
1237
1299
1337
1387
1428
1465
Power (W)
336
346
355
364
374
389
399
413
423
430
CFM
1216
1193
1168
1146
1123
1086
1062
1028
1002
975
5
RPM
1268
1301
1333
1394
1426
1473
1491
Power (W)
452
462
471
490
499
508
478
CFM
1250
1229
1208
1173
1151
1112
1036
1000
750
ECM -
Constant
Volume
Minimum CFM
RPM
872
928
990
1046
1096
1143
1192
1238
1282
1327
Power (W)
71
89
108
127
145
162
181
199
217
235
CFM
750
750
750
750
750
750
750
750
750
750
Default CFM
RPM
1131
1177
1218
1252
1295
1337
1381
1415
Power (W)
251
274
296
315
337
362
387
407
CFM
1000
1000
1000
1000
1000
1000
1000
1000
Maximum CFM
RPM
1260
1299
1334
1373
1403
Power (W)
388
410
431
453
471
CFM
1150
1150
1150
1150
1150
See ECM control section for details on setting airflow.
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidification mode if HP CFM is on setting 1.
ClimaDry is factory wired to operate in stage 2 airflow.
Black areas denote ESP where operation is not recommended.
PSC: Units factory shipped on medium speed. Other speeds require field selection.
CT ECM: Units factory shipped on Speed Tap 2 for Fan-Only and Speed Tap 3 for Heating/Cooling.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply. Performance may vary as the power supply varies from the rated.
All data is shown wet coil with clean 1” filter.
All data is ran at 80 °F DB and 67 °F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
All TR units with optional CV-ECM fan motor automatically adjusts for the reheat coil. The small
additional pressure drop of the reheat coil causes the CV-ECM motor to slightly increase RPM to
overcome the added pressure drop, and maintain selected CFM up to the maximum ESP.