Blower Performance Data – TR Hybrid 006
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
225
150
ECM -
Constant
Torque
1
RPM
1019
1081
1165
1240
1322
Power (W)
30
33
35
37
40
CFM
228
211
190
168
158
2
RPM
1265
1336
1418
1475
1545
1616
1686
Power (W)
45
48
50
53
55
58
60
CFM
241
228
211
191
179
167
159
3
RPM
1381
1454
1522
1583
1646
1715
1782
Power (W)
57
60
61
64
66
68
70
CFM
247
235
220
202
190
180
169
4
RPM
1559
1624
1683
1741
1806
Power (W)
71
74
76
78
80
CFM
244
232
220
210
195
225
150
ECM -
Constant
Volume
Minimum CFM
RPM
926
1027
1124
1231
1343
1434
1531
1638
1740
1841
Power (W)
20
25
30
35
40
45
50
55
60
65
CFM
150
150
150
150
150
150
150
150
150
150
Default CFM
RPM
1029
1137
1248
1353
1456
1569
1680
1785
1893
2001
Power (W)
40
45
50
55
60
65
70
75
80
85
CFM
225
225
225
225
225
225
225
225
225
225
Maximum CFM
RPM
1084
1185
1285
1386
1487
1587
1687
1788
1888
1989
Power (W)
33
41
50
56
60
71
80
86
93
101
CFM
250
250
250
250
250
250
250
250
250
250
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.