R e v. : 2 9 M a y, 2 0 1 5 J
ECM Blower Performance Data
Air
fl
ow in CFM with wet coil and clean air
fi
lter
Model
Max
ESP
(in. wg)
Fan
Motor
(hp)
Range
Cooling Mode
Dehumid Mode
Heating Mode
Fan
Only
Mode
Aux/
Emerg
Mode
Stg 2
Stg 1
Stg 2
Stg 1
Stg 2
Stg 1
026
1.0
1/2
Default
700
525
550
425
750
600
350
850
Maximum
1000
800
800
600
1000
850
1000
1000
Minimum
600
450
550
400
600
450
300
700
038
0.9
1/2
Default
1050
800
850
650
1100
850
550
1350
Maximum
1500
1100
1200
900
1500
1100
1500
1500
Minimum
900
600
825
550
900
600
450
1350
049
1.0
1
Default
1400
1050
1100
850
1500
1150
700
1500
Maximum
2000
1500
1600
1200
2000
1500
2000
2000
Minimum
1200
900
1100
825
1200
900
600
1350
064
0.7
1
Default
1750
1300
1400
1050
1875
1450
875
1875
Maximum
2300
1900
2000
1500
2300
1900
2300
2300
Minimum
1500
1100
1375
1000
1500
1100
750
1500
072
0.7
1
Default
1900
1450
1650
1250
2000
1650
950
2000
Maximum
2300
2200
2000
1800
2300
2200
2300
2300
Minimum
1800
1350
1650
1250
1800
1350
900
1800
Air
fl
ow is controlled within 5% up to the Max ESP shown with wet coil
Table 10: Tranquility
®
30 (TE) Series ECM Blower Performance Data Table
Содержание Tranquility 30 TE026