Horizontal Installation
Figure 3: Typical Horizontal Unit Installation
Air Coil -
To obtain maximum performance, the air coil
should be cleaned before start-up. A 10% solution of
dishwasher detergent and water is recommended for
both sides of the coil. A thorough water rinse should
follow. UV based anti-bacterial systems may damage
coated air coils.
Notice!
Installation Note - Ducted Return: Many
horizontal WSHPs are installed in a return air ceiling
plenum application (above ceiling). Vertical WSHPs are
commonly installed in a mechanical room with free return
(e.g. louvered door). Therefore, filter rails are the industry
standard and are included on ClimateMaster commercial
heat pumps for the purposes of holding the filter only. For
ducted return applications, the filter rail must be removed
and replaced with a duct flange or filter frame. Canvas
or flexible connectors should also be used to minimize
vibration between the unit and ductwork.
(by others)
Thermostat
Wiring
Ball Valve with optional
integral P/T plug
Building
Loop
Unit Power
Disconnect
Power Wiring
Insulated supply duct with
at least one 90 deg elbow
to reduce air noise
Return Air
Supply Air
Unit Hanger Kits
(included)
3/8" [10mm] threaded rods
Unit Power
Stainless steel braid hose
with integral "J" swivel
Figure 2: Horizontal Unit Pitch
1/4” (6.4mm) pitch
toward drain for drainage
Drain Connection