Tranquility
®
22 (TZ) Series
R e v. : A u g u s t 4 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
30
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
Electrical
–
Thermostat Wiring
Thermostat Installation -
The thermostat should be
located on an interior wall in a larger room, away from
supply duct drafts. DO NOT locate the thermostat in areas
subject to sunlight, drafts or on external walls. The wire
access hole behind the thermostat may in certain cases
need to be sealed to prevent erroneous temperature
measurement. Position the thermostat back plate against
the wall so that it appears level and so the thermostat
wires protrude through the middle of the back plate. Mark
the position of the back plate mounting holes and drill
holes with a 3/16” (5mm) bit. Install supplied anchors
and secure plate to the wall. Thermostat wire must be 18
AWG wire. Representative thermostat wiring is shown in
Figures 17a-b however, actual wiring connections should
be determined from the thermostat IOM and or unit wiring
diagram. Practically any heat pump thermostat will work
with ClimateMaster units, provided it has the correct
number of heating and cooling stages.
Field Wiring
Factory Wiring
Figure 17a: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC
32
U
03
C
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03C.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
24Vac Common
Gnd
R
C
A+
Figure 17b: Communicating Thermostat Connection to
DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC
32
U
03
C
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03C.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
24Vac Common
Gnd
R
C
A+