Electrical
–
Line Voltage, Cont’d.
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Pump Motor
FLA
Fan Motor
FLA
Total Unit
FLA
Min Circ
Amp
Max Fuse/
HACR
RLA
LRA
Qty
024
G
208/230/60/1
197/252
11.7
58.3
1
0.8
3.9
16.4
19.3
30
E
265/60/1
239/292
9.1
54.0
1
0.7
3.2
13.0
15.3
20
H
208/230/60/3
197/252
6.5
55.4
1
0.8
3.9
11.2
12.8
15
F*
460/60/3*
414/506
3.5
28.0
1
0.7
3.2
7.4
8.3
15
030
G
208/230/60/1
197/252
13.1
73.0
1
0.8
3.9
17.8
21.1
30
E
265/60/1
239/292
10.2
60.0
1
0.7
3.2
14.1
16.7
25
H
208/230/60/3
197/252
8.7
58.0
1
0.8
3.9
13.4
15.6
20
F*
460/60/3*
414/506
4.3
28.0
1
0.7
3.2
8.2
9.3
15
036
G
208/230/60/1
197/252
15.3
83.0
1
0.8
3.9
20.0
23.8
35
E
265/60/1
239/292
13.0
72.0
1
0.7
3.2
16.9
20.2
30
H
208/230/60/3
197/252
11.6
73.0
1
0.8
3.9
16.3
19.2
30
F*
460/60/3*
414/506
5.7
38.0
1
0.7
3.2
9.6
11.0
15
042
G
208/230/60/1
197/252
17.9
96.0
1
0.8
5.2
23.9
28.4
45
H
208/230/60/3
197/252
14.2
88.0
1
0.8
5.2
20.2
23.8
35
F*
460/60/3*
414/506
6.2
44.0
1
0.7
4.7
11.6
13.2
15
048
G
208/230/60/1
197/252
21.2
104.0
1
1.1
5.2
27.5
32.8
50
E
265/60/1
239/292
16.0
109.7
1
1.1
4.7
21.8
25.8
40
H
208/230/60/3
197/252
14.0
83.1
1
1.1
5.2
20.3
23.8
35
F*
460/60/3*
414/506
6.4
41.0
1
1.1
4.7
12.2
13.8
20
060
G
208/230/60/1
197/252
27.1
152.9
1
1.1
6.9
35.1
41.9
60
E
265/60/1
239/292
22.4
130.0
1
1.1
6.0
29.5
35.1
50
H
208/230/60/3
197/252
16.5
110.0
1
1.1
6.9
24.5
28.6
45
F*
460/60/3*
414/506
7.2
52.0
1
1.1
6.0
14.3
16.1
20
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units require a four wire power supply with neutral. ECM motor and optional
circulating pumps are rated 265 vac and are wired between one hot leg and neutral.
Units with Modulating Motorized Valve
Units with Internal Secondary Pump
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan Motor
FLA
Total Unit
FLA
Min Circ
Amp
Max Fuse/
HACR
RLA
LRA
Qty
024
G
208/230/60/1
197/252
11.7
58.3
1
3.9
15.6
18.5
30
E
265/60/1
239/292
9.1
54.0
1
3.2
12.3
14.6
20
H
208/230/60/3
197/252
6.5
55.4
1
3.9
10.4
12.0
15
F*
460/60/3*
414/506
3.5
28.0
1
3.2
6.7
7.6
15
030
G
208/230/60/1
197/252
13.1
73.0
1
3.9
17.0
20.3
30
E
265/60/1
239/292
10.2
60.0
1
3.2
13.4
16.0
25
H
208/230/60/3
197/252
8.7
58.0
1
3.9
12.6
14.8
20
F*
460/60/3*
414/506
4.3
28.0
1
3.2
7.5
8.6
15
036
G
208/230/60/1
197/252
15.3
83.0
1
3.9
19.2
23.0
35
E
265/60/1
239/292
13.0
72.0
1
3.2
16.2
19.5
30
H
208/230/60/3
197/252
11.6
73.0
1
3.9
15.5
18.4
30
F*
460/60/3*
414/506
5.7
38.0
1
3.2
8.9
10.3
15
042
G
208/230/60/1
197/252
17.9
96.0
1
5.2
23.1
27.6
45
H
208/230/60/3
197/252
14.2
88.0
1
5.2
19.4
23.0
35
F*
460/60/3*
414/506
6.2
44.0
1
4.7
10.9
12.5
15
048
G
208/230/60/1
197/252
21.2
104.0
1
5.2
26.4
31.7
50
E
265/60/1
239/292
16.0
109.7
1
4.7
20.7
24.7
40
H
208/230/60/3
197/252
14.0
83.1
1
5.2
19.2
22.7
35
F*
460/60/3*
414/506
6.4
41.0
1
4.7
11.1
12.7
15
060
G
208/230/60/1
197/252
27.1
152.9
1
6.9
34.0
40.8
60
E
265/60/1
239/292
22.4
130.0
1
6.0
28.4
34.0
50
H
208/230/60/3
197/252
16.5
110.0
1
6.9
23.4
27.5
40
F*
460/60/3*
414/506
7.2
52.0
1
6.0
13.2
15.0
20
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units require a four wire power supply with neutral. ECM motor is rated
265 vac and is wired between one hot leg and neutral.