background image

Tranquility

®

 22 (TZ) Series

R e v. :   A u g u s t   4 ,   2 0 2 1

C l i m a t e M a s t e r   Wa t e r-S o u rc e   H e a t   P u m p s

46

C L I M AT E M A S T E R  WAT E R - S O U R C E   H E AT   P U M P S

Unit Operating Condition, Cont’d.

Table 12: Water Temperature Change Through Heat Exchanger

Water Flow, gpm [l/m]

Rise, Cooling 

°F, [°C]

Drop, Heating

°F, [°C]

For Closed Loop: Ground Source or Closed Loop 

Systems at 3 gpm per ton [3.2 l/m per kW]

9 - 12

[5 - 6.7]

4 - 8

[2.2 - 4.4]

For Open Loop: Ground Water  

Systems at 1.5 gpm per ton [1.6 l/m per kW]

20 - 26

[11.1 - 14.4]

10 - 17

[5.6 - 9.4]

048

Full Load Cooling - without HWG active

Full Load Heating - without HWG active

Entering 

Water 

Temp °F

Water

Flow

GPM/ton

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Drop

°F

Air Temp

Drop °F DB

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Drop

°F

Air Temp

Rise °F 

DB

30

*

1.5

2.25

3

61-71

64-74

68-78

290-310

293-313

296-316

9-14

9-14

10-15

5-10

5-10

5-10

7.7-9.7

5.7-7.7

3.7-5.7

18-23

18-23

18-23

50

1.5

2.25

3

124-134

123-133

121-131

250-270

212-232

173-193

11-16

12-17

13-18

13-18

10-15

7-12

20.1-22.1

14.8-16.8

9.5-11.5

19-24

19-24

19-24

88-98

94-104

100-110

319-339

324-344

330-350

11-16

11-16

12-17

6-11

6-11

6-11

10.3-12.3

7.8-9.8

5.3-7.3

24-29

25-30

25-30

70

1.5

2.25

3

129-139

128-138

127-137

334-354

309-329

284-304

9-14

10-15

10-15

16-21

13-18

10-15

19.6-21.6

14.4-16.4

9.3-11.3

18-23

18-23

18-23

117-127

125-135

133-143

349-369

357-377

365-385

13-18

14-19

15-20

5-10

5-10

4-11

13.4-15.4

10.2-12.2

6.9-8.9

29-34

30-35

31-36

90

1.5

2.25

3

135-145

134-144

132-142

470-490

446-466

422-442

7-12

7-12

8-13

20-25

17-22

15-20

18.9-20.9

13.8-15.8

8.8-10.8

16-21

16-21

16-21

150-160

158-168

166-176

384-404

391-411

399-419

15-20

16-21

17-22

3-8

2-7

2-7

16.6-18.6

12.6-14.6

8.5-10.5

35-40

36-41

37-42

110

1.5

2.25

3

138-148

138-148

137-147

548-568

526-546

505-525

6-11

6-11

6-11

22-27

19-24

17-22

18.6-20.6

13.6-15.6

8.6-10.6

15-20

15-20

15-20

*

Based on 15% Methanol antifreeze solution

060

Full Load Cooling - without HWG active

Full Load Heating - without HWG active

Entering 

Water 

Temp °F

Water

Flow

GPM/ton

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Drop

°F

Air Temp

Drop °F DB

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Drop

°F

Air Temp

Rise °F 

DB

30

*

1.5

2.25

3

64-74

68-78

71-81

309-329

313-333

317-337

7-12

7-12

8-13

10-15

10-15

10-15

8.4-10.4

6.0-8.0

3.6-5.6

19-24

20-25

20-25

50

1.5

2.25

3

120-130

120-130

118-128

225-245

222-242

220-240

9-14

9-14

9-14

13-18

10-15

9-14

21.8-23.8

14.7-16.7

8.7-10.7

20-25

20-25

20-25

94-104

100-110

105-115

343-363

350-270

356-376

9-14

10-15

10-15

12-18

11-16

10-15

11.3-13.3

8.2-10.2

5.0-8.0

25-30

26-31

26-31

70

1.5

2.25

3

124-134

124-134

123-133

300-320

278-298

256-276

8-13

8-13

8-13

14-19

11-16

9-14

19.9-21.9

14.1-16.1

8.3-10.3

19-24

19-24

19-24

122-132

130-140

137-147

377-397

386-406

394-414

11-16

12-17

13-18

9-14

8-13

7-12

14.2-16.2

10.3-12.3

6.5-8.5

31-36

31-36

33-38

90

1.5

2.25

3

130-140

129-139

129-139

420-440

400-420

390-410

7-12

7-12

7-12

16-21

12-17

9-14

19.0-21.0

13.4-15.4

7.9-9.9

17-22

17-22

17-22

155-165

165-175

175-185

412-432

423-443

423-443

14-19

15-20

16-21

6-11

5-10

4-9

17.2-19.2

12.6-14.6

7.9-9.9

36-41

37-42

39-44

110

1.5

2.25

3

133-143

132-142

132-142

495-515

475-495

454-474

6-11

6-11

6-11

16-21

13-18

9-14

18.5-20.5

13.1-15.1

7.6-9.6

16-21

16-21

16-21

*

Based on 15% Methanol antifreeze solution

042

Full Load Cooling - without HWG active

Full Load Heating - without HWG active

Entering 

Water 

Temp °F

Water

Flow

GPM/ton

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Rise

°F

Air Temp

Drop °F DB

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat

Subcooling

Water

Temp Drop

°F

Air Temp

Rise °F 

DB

30

*

1.5

2.25

3

64-74

67-77

71-81

314-334

317-337

321-341

6-11

6-11

7-12

9-14

9-14

9-14

8.0-10.0

6.0-8.0

4.0-6.0

20-25

20-25

21-26

50

1.5

2.25

3

121-131

120-130

120-130

230-250

200-240

164-184

10-15

11-16

11-16

10-15

8-13

6-11

20.5-22.5

15.2-17.2

9.8-11.8

22-27

22-27

22-27

95-105

100-110

104-114

351-371

356-376

361-381

8-13

9-14

10-15

9-14

9-14

9-14

10.7-12.7

8.1-10.1

5.4-7.4

26-31

27-32

27-32

70

1.5

2.25

3

127-137

125-135

125-135

305-325

290-310

263-283

8-13

9-13

10-15

10-15

9-14

7-12

19.8-21.8

14.7-16.7

9.5-11.5

20-25

21-26

21-26

124-134

131-141

138-148

386-406

390-410

400-420

11-16

12-17

13-18

8-13

8-13

7-12

13.8-15.8

10.4-12.4

7.0-9.0

32-37

33-37

34-39

90

1.5

2.25

3

133-143

132-142

132-142

426-446

406-426

390-410

7-12

7-12

7-12

11-16

9-14

8-13

19-21

14-16

9-11

19-24

19-24

19-24

157-167

164-174

172-182

423-443

432-452

441-461

13-18

15-20

16-21

5-10

5-10

5-10

16.8-18.8

12.7-14.7

8.5-10.5

38-43

40-45

41-46

110

1.5

2.25

3

137-147

136-146

136-146

494-514

477-497

460-480

5-10

6-11

6-11

11-16

10-15

8-13

18-20

14-16

9-11

18-23

18-23

18-23

*

Based on 15% Methanol antifreeze solution

Содержание Tranquility 22 TZ Series

Страница 1: ...ring 28 Electrical Low Voltage Wiring for non vFlow Units Using External Motorized Water Valve 29 Electrical Thermostat Wiring 30 Blower Performance Data 31 ECM Blower Control 32 TZ Series Wiring Diag...

Страница 2: ...Tranquility 22 TZ Series Rev Au gu st 4 2021 ClimateMaster Water Source Heat Pumps 2 C LI MATE MASTER WATER SOURCE HEAT PUMPS This Page Intentionally Left Blank...

Страница 3: ...eel Drain Pan T Right Return Stainless Steel Drain Pan M DXM2 w LON K DXM2 w LON P DXM2 w MPC w DISCONNECT S DXM2 w MPC OPTION 1 A J K 2 C L M 3 E N P 1 FILTER RACK RANGE ULTRA QUIET 2 FILTER RACK 1 F...

Страница 4: ...y damage NOTICE Notification of installation operation or maintenance information which is important but which is not hazard related Inspection Upon receipt of the equipment carefully check the shipme...

Страница 5: ...and Maintenance instructions are provided with each unit Horizontal equipment is designed for installation above false ceiling or in a ceiling plenum Other unit configurations are typically installed...

Страница 6: ...l Dimensions h x w in 20 X 17 25 20 X 17 25 24 X 21 75 24 X 21 75 28 75 X 24 28 75 X 24 Standard Filter 1 25 4mm Throwaway qty in 20x20 20x20 24x24 24x24 28x28 28x28 Weight Operating lbs 216 224 249 2...

Страница 7: ...sation such as unconditioned spaces subject to 100 outside air Consideration should be given to access for easy removal of the filter and access panels Provide sufficient room to make water electrical...

Страница 8: ...Return Right View Air Coil Opening Air Coil C B R Q Front L N O M Left Return Straight Discharge Front BSP LEFT RETURN RIGHT RETURN Air Coil CSP Front Left Return Left View Filter Rails Removed See Af...

Страница 9: ...mechanical room with free return e g louvered door Therefore filter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only...

Страница 10: ...anel 2 Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for t...

Страница 11: ...FLOW CAUTION Duct System Installation Proper duct sizing and design is critical to the performance of the unit The duct system should be designed to allow adequate and even airflow through the unit d...

Страница 12: ...hanical room closet Vertical units are typically installed in a mechanical room or closet Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation suc...

Страница 13: ...d pitched away from the unit to allow for proper drainage This connection must meet all local plumbing building codes Install condensate trap at each unit with the top of the trap positioned below the...

Страница 14: ...conditions Insulation is required if loop water temperature drops below the dew point insulation is required for ground loop applications in most climates Pipe joint compound is not necessary when Tef...

Страница 15: ...differential type of loops This valve is a factory installed option for the TZ unit and when selected replaces the modulating valve 3 Standard Head Variable Pump Typical for Multiple Unit Central Pump...

Страница 16: ...1 27 2 94 4 7 200 7 9 2 83 6 53 4 7 200 10 5 4 99 11 53 048 4 7 200 6 0 1 63 3 76 4 7 200 9 0 3 67 8 47 4 7 200 12 0 6 52 15 06 060 7 4 200 7 0 89 2 06 7 4 200 10 5 2 01 4 64 7 4 200 14 0 3 58 8 26 Mo...

Страница 17: ...Tranquility 22 TZ Series Rev A u g u st 4 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY High Head Variable Pump Performance 0 5 10 15 20 25 30 35 40 45 0 5 10 15 20 25 Head ft Flow gpm No Check Va...

Страница 18: ...flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning and Flushing Procedures in this manual The flow rate is usually set between 2 25 and 3 5 g...

Страница 19: ...nd glycols are commonly used as antifreeze however your local sales office should be consulted to determine the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 C b...

Страница 20: ...High and Low Voltage Knockouts Vibration Isolation Pad To Thermostat Internal Motorized Modulating Valve Water Out Shut Off Ball Valves for Isolation Water In Pressure Tank Optional Filter Boiler Drai...

Страница 21: ...dards Table 3 should be consulted for water quality requirements Scaling potential should be assessed using the pH Calcium hardness method If the pH 7 5 and the calcium hardness is less than 100 ppm s...

Страница 22: ...second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typically a brass fitting with an orifice of rubber or plastic material that...

Страница 23: ...ture Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging P...

Страница 24: ...on and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate Line and low voltage wiring must be done...

Страница 25: ...EUTRAL CONNECTION REQUIRED All F Voltage 460 vac units require a four wire power supply with neutral ECM motor and optional circulating pumps are rated 265 vac and are wired between one hot leg and ne...

Страница 26: ...0 3 197 252 16 5 110 1 1 44 6 9 24 8 29 0 45 Wire length based on one way measurement with 2 voltage drop Wire size based on 60 C copper conductor All fuses Class RK 5 Units with Standard Head Variabl...

Страница 27: ...r correct fuse size 460 volt units require a neutral wire Transformer All 208 230 voltage units are factory wired for 208 volt If supply voltage is 230 volt installer must rewire transformer See wire...

Страница 28: ...s shown in the tables below Accessory Relay 2 Configuration Accessory Relay 1 Configuration DIP 2 1 DIP 2 2 DIP 2 3 ACC1 Relay Option ON ON ON Cycle with fan OFF ON ON N A for Residential Applications...

Страница 29: ...ter Valve Figure 14 AVM Valve Wiring Figure 15 Taco SBV Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown Solenoid Valve Flow Regulator To Di...

Страница 30: ...ECM automatic dehumidi cation mode operates with dehumidi cation air ows in the cooling mode when the dehumidi cation output from thermostat is active Normal heating and cooling air ows are not affect...

Страница 31: ...525 750 525 750 525 375 750 036 0 6 1 2 Default 1125 750 975 650 1125 750 525 1125 Maximum 1250 950 1200 800 1250 1250 1250 1250 Minimum 900 600 900 600 900 600 450 900 042 0 6 3 4 Default 1300 925 1...

Страница 32: ...ond Stage Cooling in Dehumidification Mode Y1 Y2 O Dehumid First Stage Heating Y1 Second Stage Heating Y1 Y2 Third Stage Auxiliary Heating Y1 Y2 W Emergency Heating W with no Y1 or Y2 Fan G with no Y1...

Страница 33: ...am Matrix All current diagrams can be located online at climatemaster com commercial literature wiring diagrams Unit Controller Fan Motor 208v 1 265v 1 208v 3 460v 3 TZ024 060 TZ024 060 TZ024 060 DXM2...

Страница 34: ...d Pump DIP Switches Note In the following field configuration options DIP switches should only be changed when power is removed from the DXM2 control DIP Package 1 S1 DIP Package 1 has 8 switches and...

Страница 35: ...n off during cooling stage 2 IF the H input is active In high fan mode the fan enable and fan speed relays will turn on when the H input is active On Auto dehumidification mode default Off High fan mo...

Страница 36: ...ult LED and Status Operation with Test Mode Active Fault LED Red Status LED Green Alarm Relay No Fault Since Power Up In Memory Flashing Code 1 Cycling Code 1 High Pressure Fault In Memory Flashing Co...

Страница 37: ...ac Fan Speed N O N C 12V OUT Gnd P8 IN NC P12 1 Note There is only one T1 connection 1 2 3 4 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Service tool connection Communicating stat connection Conventional stat con...

Страница 38: ...nti short cycle delay at power up The first time after power up that there is a call for compressor the compressor will follow a 5 to 80 second random start delay After the random start delay and anti...

Страница 39: ...70 158 0 1 75 1 33 8 31 03 71 159 8 1 69 2 35 6 29 50 72 161 6 1 64 3 37 4 28 05 73 163 4 1 58 4 39 2 26 69 74 165 2 1 53 5 41 0 25 39 75 167 0 1 48 6 42 8 24 17 76 168 8 1 43 7 44 6 23 02 77 170 6 1...

Страница 40: ...omplies with AHRI Standard 110 Table 8 Operating Limits Operating Limits TZ Cooling Heating Air Limits Min ambient air DB 45 F 7 C 39 F 4 C Rated ambient air DB 80 6 F 27 C 68 F 20 C Max ambient air D...

Страница 41: ...he solution for a minimum of 8 to 24 hours At the end of this period shut off the circulating pump and drain the solution Repeat system cleaning if desired 8 When the cleaning process is complete remo...

Страница 42: ...and fittings see table 3 System flushing Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger water valves and other components Water us...

Страница 43: ...paring the pressure drop across the heat exchanger to table 10 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operatin...

Страница 44: ...me areas of the electrical panel Exercise caution when working with energized equipment CAUTION Verify that ALL water control valves are open and allow water flow prior to engaging the compressor Free...

Страница 45: ...8 98 96 106 105 115 353 373 361 381 370 390 9 14 10 15 10 15 14 19 14 19 14 19 13 2 15 2 9 0 11 0 4 8 6 8 24 29 25 30 26 31 70 1 5 2 25 3 128 138 124 134 119 129 310 330 290 310 270 290 10 15 10 15 11...

Страница 46: ...333 317 337 7 12 7 12 8 13 10 15 10 15 10 15 8 4 10 4 6 0 8 0 3 6 5 6 19 24 20 25 20 25 50 1 5 2 25 3 120 130 120 130 118 128 225 245 222 242 220 240 9 14 9 14 9 14 13 18 10 15 9 14 21 8 23 8 14 7 16...

Страница 47: ...Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor...

Страница 48: ...Inputs All sensor inputs are paired wires connecting each component to the board Therefore continuity on pressure switches for example can be checked at the board connector The thermistor resistance...

Страница 49: ...ssed from the Installer menu For more detailed information on the advanced diagnostics of the DXM2 see the DXM2 Application Operation and Maintenance AOM manual part 97B0003N15 DXM2 Troubleshooting Pr...

Страница 50: ...uns Start Did Unit Attempt to Start Did Unit Lockout at Start up Unit Short Cycles Only Fan Runs Only Compressor Runs Did unit lockout after a period of operation Does unit operate in cooling Unit is...

Страница 51: ...X X Bad thermistor Check temp and impedance correlation per chart LT2 Fault Code 5 Air coil low temperature limit X Reduced or no air flow in cooling Check for dirty air filter and clean or replace C...

Страница 52: ...vs blower table Air temperature out of range Too much cold vent air bring entering air temp within design parameters Bad thermistor Check temp and impedance correlation per chart ESD ERV Fault DXM On...

Страница 53: ...moisture X Air temperature out of range in heating Bring return air temp within design parameters X Scaling in water heat exchanger Perform Scaling check and clean if necessary X X Unit over charged C...

Страница 54: ...of external static check static vs blower table X X Leaky duct work Check supply and return air temperatures at the unit and at distant duct registers if significantly different duct leaks are presen...

Страница 55: ...Settings ECM Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Temperature DB...

Страница 56: ...S COAX COMPRESSOR DISCHARGE SUCTION HWG HEATING CYCLE ANALYSIS PSI SAT PSI SAT F F AIR COIL F F FP2 HEATING LIQUID LINE F EXPANSION VALVE AIR COIL F F PSI SAT PSI SAT F F F F WATER IN WATER OUT PSI PS...

Страница 57: ...suf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair...

Страница 58: ...s damage or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increa...

Страница 59: ...climatemaster com 59 Tranquility 22 TZ Series Rev A u g u st 4 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Notes...

Страница 60: ...tory Date Item Action 08 04 21 Page 8 Added Horizontal Dimensional Data 07 08 21 All Updated to include polymer drain pan 12 11 19 All Misc Table and Figure updates 12 02 19 Pages 3 15 16 Updated for...

Отзывы: