R e s i d e n t i a l H & V - 6 0 H z H F C - 4 1 0 A
R e v. : 9 M a r c h , 2 0 1 1 B
28
G e o t h e r m a l H e a t P u m p S y s t e m s
Tranquility 20™ (TS) Series ECM Blower Performance Data
Residential
Units Only
Model
Max
ESP
(in. wg)
Fan
Motor
(hp)
Tap
Setting
Cooling Mode
Dehumid Mode
Heating Mode
AUX
CFM
Aux/
Emerg
Mode
Stg 1
Stg 2
Fan
Stg 1
Stg 2
Fan
Stg 1
Stg 2
Fan
018
0.50
1/2
4
620
750
380
480
590
380
620
750
380
4
750
3
570
700
350
450
550
350
570
700
350
3
700
2
510
620
310
400
480
310
510
620
310
2
650
1
430
530
270
430
530
270
1
650
024
0.50
1/2
4
780
950
470
610
740
470
870
1060
470
4
1060
3
700
850
420
540
660
420
780
950
420
3
950
2
630
770
360
490
600
360
670
820
390
2
820
1
550
670
300
570
690
340
1
690
030
0.50
1/2
4
920
1130
560
720
880
560
1000
1230
560
4
1230
3
820
1000
500
640
780
500
900
1100
500
3
1100
2
740
900
450
580
700
450
800
980
450
2
980
1
660
800
400
700
850
400
1
850
036
0.50
1/2
4
1150
1400
700
900
1090
700
1150
1400
700
4
1400
3
1020
1250
630
800
980
630
1020
1250
630
3
1350
2
890
1080
540
690
840
540
890
1080
540
2
1350
1
740
900
450
750
920
450
1
1350
042
0.50
1/2
4
1290
1580
790
1010
1230
790
1290
1580
790
4
1580
3
1150
1400
700
900
1090
700
1150
1400
700
3
1400
2
1050
1280
640
820
1000
640
1020
1240
640
2
1350
1
920
1120
560
900
1080
560
1
1350
048
0.75
1
4
1420
1730
870
1110
1350
870
1520
1850
865
4
1850
3
1270
1550
780
990
1210
780
1350
1650
775
3
1650
2
1180
1440
720
920
1120
720
1190
1450
720
2
1450
1
1050
1280
640
1020
1250
640
1
1350
060
0.75
1
4
1680
2050
1030
1310
1600
1030
1870
2280
1030
4
2280
3
1500
1830
910
1170
1420
910
1680
2050
910
3
2050
2
1400
1700
850
1090
1330
850
1480
1800
850
2
1800
1
1300
1580
790
1270
1550
790
1
1550
070
0.75
1
4
1830
2230
1100
1420
1740
1100
1830
2230
1100
4
2230
3
1600
1950
980
1250
1520
980
1720
2100
980
3
2100
2
1440
1750
880
1120
1360
880
1670
1950
880
2
1950
1
1200
1580
790
1460
1780
790
1
1780
Bold numbers indicate factory settings.
During Auxiliary operation the CFM will run at the higher of the Heating (Delay jumper) or AUX settings.
Airfl ow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidifi cation mode if HP CFM is on setting 1.
All units AHRI/ISO/ASHRAE 13256-1 rated HP CFM Setting 3.
Note: See the ECM Blower Control section for information on setting taps.
Airfl ow in CFM with wet coil and clean air fi lter