Engineering Guide Specifications
General
Factory-assembled and wired water cooled, water chiller .
Chiller consists of two compressors, one evaporator and
condenser, safety and operational controls . The modular
water cooled package chiller shall incorporate one or more
modules with two independent refrigerant circuits . Modules
shall be capable of independent operation powered by a
field installed fused disconnect switch (or equivalent circuit
breaker) supplied by others, so that any one module can
be shut down for repair without interrupting the remaining
chiller modules in operation .
Basic Construction
The frame design shall consist of heavy gauge galvanized
steel with 3 mil powder coat paint finish baked at 350° for
resilience in transport and installation . The module must
have a low center of gravity, detachable schedule 40 carbon
steel pipe water headers, designed to connect to adjacent
modules through the use of 300 psi rated grooved cou-
plings, base with cutouts for forklift or pallet jack and the
frame must be designed to fit through a standard 36”
doorway . Each module has sound attenuation panels to
ensure quiet operation .
Refrigeration Circuit
All refrigeration circuits shall contain R-410A non-ozone
depleting HFC . Each independent circuit shall consist of a
scroll compressor, thermostatic expansion valve for
refrigerant metering, sight glass, filter drier and high and
low pressure safety controls . The modular chiller bank must
be able to produce chilled water even in the event of a
failure of one or more refrigerant circuits .
Evaporator
Each evaporator shall be highly efficient, refrigerant-
to-water, dual circuited, brazed plate heat exchangers
constructed of 300 stainless steel; designed, tested, and
UL stamped in accordance with ASME Section VIII pressure
vessel code for 650 psig working refrigerant pressure .
The evaporator heat exchanger shall be mounted to
eliminate the effect of migration of refrigerant to the cold
evaporation with consequent liquid slugging on startup .
The evaporator shall be mounted on two layers of noise
attenuating rubber isolation pads which also act as a
thermal barrier. The evaporator shall be wrapped with ¾”
closed cell insulated blanket . The closed cell insulation s
hall be provided on suction side refrigerant tubing
including refrigerant-to-chiller heat exchanger to
prevent condensation
Condenser
Each condenser shall be highly efficient, refrigerant-
to-water, dual circuited, brazed plate heat exchangers
constructed of 300 stainless steel; designed, tested, and
UL stamped in accordance with ASME Section VIII pressure
vessel code for 650 psig working refrigerant pressure on
the condenser . The condenser heat exchanger shall be
mounted to eliminate the effect refrigerant migration to
the cold evaporation with consequent liquid slugging on
startup . The condenser shall be mounted on two layers of
noise attenuating rubber isolation pads which also acts as a
thermal barrier .
Compressors
Each module shall contain two scroll compressors
independently circuited for redundancy . Each compressor
shall be mounted with rubber isolated compressor mounts
to the module base and each shall include compressor
overload protection, high discharge pressure and low
suction pressure cutouts .
Control Panel
Master Controllers shall be provided for individual control
as well as system integration . The control shall consist of
a simple two-conductor shielded daisy chain connection to
allow communication between modules with minimal field
wiring . The remote air cooled chiller control panel shall
be a NEMA Type 1 enclosure including: power distribution
block, compressor fusing, contactors, finger safe control
fusing, transformer, isolation relays, status and alarm
relay, 16-bit microprocessor master controller with built in
native Building Automation System (BAS) communication
protocols, (BACnet, LonWorks, Modbus and N2), status
indicating lights showing: 1) compressor operation (on/off),
2) unit alarm status, 3) power on, two toggle switches to
disable each individual compressor during start-up
or troubleshooting .
CoolLogic
Control System
Remote Master Control system shall be fully compatible
with the Building Automation System via native BACnet and
LonWorks, Modbus and N2 communication . Scheduling
of the various compressors shall be performed by the
master microprocessor based controller . A compressor
run time equalization sequence is provided to ensure even
distribution of compressor run time . A load limit control
shall be available to limit the number of compressors that
can be energized at one time .
The
CoolLogic
Control System shall monitor and report the
following for each refrigeration circuit in each module:
• Discharge pressure and temperature faults
• Suction pressure and temperature faults
• Compressor winding high temperature fault
• Low evaporator leaving chilled water temperature fault
Содержание UCH 30
Страница 16: ... www climacoolcorp com 14 Voltage Phase Monitor Wiring ...
Страница 21: ...19 www climacoolcorp com Figure 23 Part Load Performance Advantage ...
Страница 57: ...55 www climacoolcorp com Wiring Diagrams 030 050 070 Cooling Only ...
Страница 58: ... www climacoolcorp com 56 Wiring Diagrams 030 050 070 Cooling Only ...
Страница 59: ...57 www climacoolcorp com Wiring Diagrams 030 050 070 Heat Pump ...
Страница 60: ... www climacoolcorp com 58 Wiring Diagrams 030 050 070 Heat Pump ...
Страница 61: ...59 www climacoolcorp com Wiring Diagrams 085 Cooling Only ...
Страница 62: ... www climacoolcorp com 60 Wiring Diagrams 085 Cooling Only ...
Страница 63: ...61 www climacoolcorp com Wiring Diagrams 085 Heat Pump ...
Страница 64: ... www climacoolcorp com 62 Wiring Diagrams 085 Heat Pump ...
Страница 65: ...63 www climacoolcorp com Wiring Diagrams Master Panel ...
Страница 66: ... www climacoolcorp com 64 Wiring Diagrams Master Panel ...
Страница 70: ... www climacoolcorp com 68 Notes ...
Страница 71: ...69 www climacoolcorp com Notes ...