www.climacoolcorp.com
8
Recommended Service Clearances
Notes:
1 . Allow 36" clearance for electrical panels and 30" clearance for rear service access to modules .
2 . Allow a minimum of 18" height clearance for 30, 50 and 70 ton modules . Allow a minimum of 24” height clearance for 85 ton modules .
3 . Local building and/or electrical codes may require additional clearance . Consult applicable codes .
CoolLogic
Control Panel
(Wall Mounted)
Top View
Rear Service Access
Front Service Access
36”
36”
30”
30”