3.0

ADJUSTMENTS

3.4.1 TLD Low Limit Calibration - Put TLD select
switch to L position. In order for the TLD circuit to
operate, the TLD switch on the front cover must be on
(illuminated). If the switch is off the TLD function is
bypassed.

The tension limit detector level (2P) on the TLD card
should be adjusted slightly below the minimum operating
tension. The tension limit detector delay (1P) on the
TLD card should be adjusted for the minimum time
delay without causing the TLD relay to trip on normal
tension transients.

When the tension drops below the tension limit detector
level set point, a set of normally open and normally
closed  relay contacts on the TLD card will switch
states.

3.4.2 TLD High Limit Calibration - Put TLD select
switch to H position. In order for the TLD circuit to
operate, the TLD switch on the front cover must be on
(illuminated). If the switch is off the TLD function is
bypassed.

The tension limit detector level (2P) on the TLD card
should be adjusted slightly above the maximum operating
tension. The tension limit detector delay (1P) on the
TLD card should be adjusted for the minimum time
delay without causing the TLD relay to trip on normal
tension transients.

When the tension rises above the tension limit detector
level set point, a set of normally open and normally
closed  relay contacts on the TLD card will switch
states.

3.5

ISOLATION AMPLIFIER OPTION

Mount the isolation amplifier card to the indicator circuit
board with the four plastic standoffs as shown in Figure
2. Connect the short 3 wire cable from 2TB on the
isolation amplifier card to 3TB on the indicator circuit
board.

Position the switch on the isolation amplifier card to the
0-10V position for a 0 to 10 VDC isolated tension output
signal, or to the 4-20mA position for a 4-20mADC
isolated tension output signal.

3.6.1 Decimal Point Selection

3.6

DIGITAL TENSION METER

A signal conditioning circuit is included on the indicator
circuit board for displaying the tension on a digital meter.
The moveable jumper on the circuit board should be in
position 7J.

When the 0-10 VDC tension output signal is fed to 1TB-
10 on the circuit board a conditioned adjustable 0 to 2
VDC for the digital meter is present at 1TB-11.

Potentiometer 5P of the signal conditioning circuit
normally is factory adjusted for a 0-1 VDC output with
a  0-10 VDC tension output signal as an input. This
allows a 3½ digit 0-2 VDC digital meter to display 100.0
at full scale.

By adjusting 5P, the full scale reading on the 2 VDC
digital panel meter can be changed to any reading
between 35.0 to 199.9 with a 10 VDC tension output 
signal present at 1TB-10.

Содержание Cleveland-Kidder TMI

Страница 1: ...VAC resistive each limit Optional Isolation 0 10 VDC 5 mA or 4 to Amplifier 20 mADC 1500 VRMS Optional 2000V peak isolated Ambient Temperature 0 40EC 32 104EF Relative Humidity 5 to 95 w o condensatio...

Страница 2: ...2 of 18 A800 7425 J Figure 1 1 0 GENERAL INFORMATION...

Страница 3: ...provides an isolated 0 10 VDC or a 40 20mADC output 1 3 4 Digital AnalogMeter Blank Plate Option A 3 inch digit panel meter or a 5 inch analog meter are available The blank meter plate can be install...

Страница 4: ...stment for the digital between 22TB on the isolation amplifier and 3TB tension meter display on the indicator main circuit board It supplies power to operate the isolation amplifier 10 Isolation Ampli...

Страница 5: ...the signals in the indicator The Tensi Master indicators can also be used for cantilever wire and single transducer applications 1 0 GENERAL INFORMATION 2 0 INSTALLATION AC VOLTS JUMPER 100 2TB 23 TO...

Страница 6: ...n Insert the line cord into the rectangular hole in the bottom of the enclosure Refer to Figure 4 Make the following connections to terminal block 1TB Brown wire to L1 Blue wire to L2 Green wire to G...

Страница 7: ...k through this conduit See Figure 5 3 0 ADJUSTMENTS Check that the indicator has been wired correctly per the installation wiring diagram and that the jumper at 2TB is set for the proper line voltage...

Страница 8: ...will cause inaccurate calibration B Apply a known tension load using weights or a spring scale If possible the applied load should be approximately the same as the anticipated operating tension If fo...

Страница 9: ...rises above the tension limit detector level set point a set of normally open and normally closed relay contacts on the TLD card will switch states 3 5 ISOLATION AMPLIFIER OPTION Mount the isolation a...

Страница 10: ...the maximum working force of the transducers in most cases 4 2 LOW OUTPUT SIGNAL The transducer may have too large a maximum working force for the application Replace with a lower maximum working forc...

Страница 11: ...ransducer instruction manual 5 0 REPLACEMENT PARTS Description Use P N Lamp Power ON OFF X01 21443 Switch PB Power ON OFF X16 11705 Lens Red Power ON OFF X01 21442 Lamp 28V TLD X01 11702 Switch PB TLD...

Страница 12: ...12 of 18 A800 7425 J 7 0 OUTLINE DIMENSIONS...

Страница 13: ...13 of 18 A800 7425 J 7 0 OUTLINE DIMENSIONS...

Страница 14: ...ALS 1 2 NORMALLY CLOSED AND 3 4 NORMALLY OPEN WHEN TENSION IS WITHIN THE NORMAL OPERATING LIMITS EACH CONTACT IS RATED AT 5 AMP 115 VAC RESISTIVE 1 2 3 4 5 6 7 8 9 10 11 T L D CARD T L D A B 2 4 3 1 O...

Страница 15: ...15 of 18 A800 7425 J INSTRUCTION m m A800 7425 J Page 1 of 16 8 0 INSTALLATION WIRING DIAGRAM...

Страница 16: ...16 of 18 A800 7425 J 8 0 INSTALLATION WIRING DIAGRAM...

Страница 17: ...COMPANY WITHIN THE APPLICABLE WARRANTY PERIOD OR B DUE TO MISAPPLICATION M O D I F I C A T I O N DISASSEMBLY ABUSE M I S U S E I M P R O P E R I N S T A L L A T I O N UNAUTHORIZED REPAIR IMPROPER MAI...

Страница 18: ...HERE ANY MATERIAL OR WORKMANSHIP DEFECTS WHICH BECOME APPARENT WITHIN ONE YEAR FROM THE DATE ON WHICH THE GOODS WERE SHIPPED THE COMPANY SHALL NOT BE LIABLE FOR SPECIAL INCIDENTAL OR CONSEQUENTIAL DAM...

Отзывы: