background image

8 of 18

A800-7425 J

Figure 6

3.0 ADJUSTMENTS

the right transducer. Calibrate the left transducer with 

be suitable to calibrate using a 100 lb. weight (or

the TRL switch in the left position and calibrate the right

100 lbs. force on a spring scale).

transducer with the TRL switch in the right position.

With a screwdriver, turn the calibrate adjustment

meter needle to the desired reading.

potentiometer ¾ clockwise. Using the zero adjustment
potentiometer, zero the tension meter.

D.

Remove the load. The meter should return to zero.

Check to see that the system is operating properly by

and C again checking meter zero. Two or three

applying a force to the sensing roll. Pushing or pulling in

load applications are sometimes required to

the load direction of the web force should cause the

properly  "seat" the transducers. With all

tension meter to move up scale.

adjustments completed, remove any cords and

3.3 CALIBRATION

The unit should be calibrated so that normal running
tensions will be about mid-scale and the maximum
tensions will not go off scale.

For TRL models, calibrate each transducer for about
25% of scale so that the total signal is about mid-scale.

NOTE:

  It is recommended that the indicators be

calibrated with the transducers at the process operating
temperature.

Spring Scale or Weight Method of Calibration

A.

Thread a length of rope or flat webbing over the
center of the sensing roll, as shown in Figure 6. Do
not thread over non-turning rollers, driven rolls, or
frame braces as any sliding friction will cause
inaccurate calibration.

B.

Apply a known tension load using weights or a
spring scale. If possible, the applied load should be
approximately the same as the anticipated
operating tension. If, for example, a normal
operating tension of 100 lbs is anticipated, it would

C.

Using the CALIBRATE adjustment bring the

If necessary, readjust ZERO then repeat steps B

weights used in the calibration procedure.

If it is found during running that the operating tension is
much less (or greater) than estimated, a recalibration
may be required.

3.3.1 Calibration with Dual Range (Scale X4) Feature
- The calibration procedure is similar to that for standard
indicators except that the calibration should be made on
the most sensitive scale (lower scale). For example, with
0-25/0-100 meter scale, calibrate on the 0-25 scale.

3.3.2 Calibration with TRL Feature - The calibration
procedure is similar to that for standard indicators. Note
that the calibration procedure can be made in either of
two ways. The quickest method is to apply a known
tension load exactly midway between the transducers.
Then calibrate on each side for ½ of the load. That is,
with the indicator on TOTAL apply a known load for
example, 50 Lbs. Switch to RIGHT and calibrate so the
meter reads 25 Lbs. Switch to LEFT and again calibrate
to 25 Lbs. If necessary, repeat the calibration.

Calibration can also be made by applying loads
simultaneously to both transducers. The TOTAL should
always be equal to the sum of the two applied loads.

3.4

CALIBRATION OF THE TLD CARD
OPTION

If the TLD card is not installed, mount it with the four
plastic standoffs to the indicator circuit board assembly
as shown in Figure 2. Connect a TLD on-off switch as
shown in Figure 2.

Содержание Cleveland-Kidder TMI

Страница 1: ...VAC resistive each limit Optional Isolation 0 10 VDC 5 mA or 4 to Amplifier 20 mADC 1500 VRMS Optional 2000V peak isolated Ambient Temperature 0 40EC 32 104EF Relative Humidity 5 to 95 w o condensatio...

Страница 2: ...2 of 18 A800 7425 J Figure 1 1 0 GENERAL INFORMATION...

Страница 3: ...provides an isolated 0 10 VDC or a 40 20mADC output 1 3 4 Digital AnalogMeter Blank Plate Option A 3 inch digit panel meter or a 5 inch analog meter are available The blank meter plate can be install...

Страница 4: ...stment for the digital between 22TB on the isolation amplifier and 3TB tension meter display on the indicator main circuit board It supplies power to operate the isolation amplifier 10 Isolation Ampli...

Страница 5: ...the signals in the indicator The Tensi Master indicators can also be used for cantilever wire and single transducer applications 1 0 GENERAL INFORMATION 2 0 INSTALLATION AC VOLTS JUMPER 100 2TB 23 TO...

Страница 6: ...n Insert the line cord into the rectangular hole in the bottom of the enclosure Refer to Figure 4 Make the following connections to terminal block 1TB Brown wire to L1 Blue wire to L2 Green wire to G...

Страница 7: ...k through this conduit See Figure 5 3 0 ADJUSTMENTS Check that the indicator has been wired correctly per the installation wiring diagram and that the jumper at 2TB is set for the proper line voltage...

Страница 8: ...will cause inaccurate calibration B Apply a known tension load using weights or a spring scale If possible the applied load should be approximately the same as the anticipated operating tension If fo...

Страница 9: ...rises above the tension limit detector level set point a set of normally open and normally closed relay contacts on the TLD card will switch states 3 5 ISOLATION AMPLIFIER OPTION Mount the isolation a...

Страница 10: ...the maximum working force of the transducers in most cases 4 2 LOW OUTPUT SIGNAL The transducer may have too large a maximum working force for the application Replace with a lower maximum working forc...

Страница 11: ...ransducer instruction manual 5 0 REPLACEMENT PARTS Description Use P N Lamp Power ON OFF X01 21443 Switch PB Power ON OFF X16 11705 Lens Red Power ON OFF X01 21442 Lamp 28V TLD X01 11702 Switch PB TLD...

Страница 12: ...12 of 18 A800 7425 J 7 0 OUTLINE DIMENSIONS...

Страница 13: ...13 of 18 A800 7425 J 7 0 OUTLINE DIMENSIONS...

Страница 14: ...ALS 1 2 NORMALLY CLOSED AND 3 4 NORMALLY OPEN WHEN TENSION IS WITHIN THE NORMAL OPERATING LIMITS EACH CONTACT IS RATED AT 5 AMP 115 VAC RESISTIVE 1 2 3 4 5 6 7 8 9 10 11 T L D CARD T L D A B 2 4 3 1 O...

Страница 15: ...15 of 18 A800 7425 J INSTRUCTION m m A800 7425 J Page 1 of 16 8 0 INSTALLATION WIRING DIAGRAM...

Страница 16: ...16 of 18 A800 7425 J 8 0 INSTALLATION WIRING DIAGRAM...

Страница 17: ...COMPANY WITHIN THE APPLICABLE WARRANTY PERIOD OR B DUE TO MISAPPLICATION M O D I F I C A T I O N DISASSEMBLY ABUSE M I S U S E I M P R O P E R I N S T A L L A T I O N UNAUTHORIZED REPAIR IMPROPER MAI...

Страница 18: ...HERE ANY MATERIAL OR WORKMANSHIP DEFECTS WHICH BECOME APPARENT WITHIN ONE YEAR FROM THE DATE ON WHICH THE GOODS WERE SHIPPED THE COMPANY SHALL NOT BE LIABLE FOR SPECIAL INCIDENTAL OR CONSEQUENTIAL DAM...

Отзывы: