PV ez-Rack Commercial Tilt spacing Table 1.3
Type of Rail
ER-R-ECO (ECO Rail) and all other ECO rails
Type of Interface
ER-I-05 (Tin Interface)
Solar Panel Dimension
2 m x 1 m
Purlin Thickness
1.9 mm
Roof Angle - 20° <
α
< 30°
TC
3
2.5
2
BUILDING
HEIGHT
< 5 5<H<10 10<H<15 15<H<20 20<H<30 < 5 5<H<10 10<H<15 15<H<20 20<H<30 < 5 5<H<10 10<H<15 15<H<20 20<H<30
WRA
1.07
1.07 1.02 0.98 0.93
1.04
1.00 0.96 0.93 0.90
1.00
0.93 0.90 0.88 0.86
WRB
0.90
0.90 0.86 0.82 0.71
0.87
0.84 0.76 0.70 0.63
0.84
0.71 0.64 0.61 0.57
WRC
0.71
0.44 0.38 0.34 0.30
0.64
0.36 0.32 0.29 0.27
0.59
0.30 0.28 0.26 0.24
WRD
0.27
0.27 0.23 0.21 0.19
0.25
0.22 0.20 0.18 0.17
0.22
0.19 0.17 0.16 0.15
Note: The above spacings are for Internal Zone. Refer to Note
15
for Intermediate, Edge and Corner Zones.