background image

APOLLO 60 HP SUPPLIED-AIR RESPIRATOR

Page 7

monoxide removal or conversion system may also be used
to ensure breathing air quality. The maximum allowable
presence of carbon monoxide in Grade D breathing air is
10 parts per million (ppm).

4.2

Air Volume and Pressure

4.2.1

A pressure regulator and gauge must be installed

at the point where the respirator hose is attached to the air
source. The Clemco CPF Filter with regulator meets this
requirement if the inlet pressure does not exceed 125 psi.
See typical installation,  Figure 1.

! DANGER

Do not connect the Apollo Respirator or CPF
Filter, or any other regulator or filter, to bottled air
that does not have a pressure reducing valve that
reduces pressure to maximum of 125 psi (65 to
100 psi for the respirator only). Failure to comply
with this warning will cause devices rated at
lower pressures to explode under the high pres-
sure of bottled air. Such an explosion could cause
severe injury or death.

4.2.2

The respirator must be supplied with 15 cfm (cubic

feet per minute) of Grade D breathing air at 65 to 100 psi
(pounds per square inch).  When using an alternate Cool-
Air Tube or Climate Control Tube, the respirator must be
supplied with 20 cfm of Grade D breathing air at 90 to 100
psi.

4.2.3

The pressure regulator must be adjusted to 65 to

100 psi. Refer to the table in Section 4.2.4 to determine the
minimum pressure, based on the total length of respirator
hose, and choice of air control device. Adjust the pressure
with the respirator hose and respirator attached. If the
regulator is adjusted with static pressure (no air flow),
pressure may drop below the required pressure when the
respirator is connected, and may result in low air flow.
Setting the pressure as instructed will provide a minimum
of 7 cfm to the respirator.

4.2.4

Use the table below to determine the minimum

pressure setting and maximum respirator hose length,
based on the air control device as shown in Section 1.7.2.

Hose

Minimum Pressure Setting, psi

Length

CFC

ACV

CCT

CAT

25 ft.

65

85

90

90

 50 ft.

65

85

90

90

75 ft.

65

85

90

90

100 ft.

65

85

95

95

125 ft.

70

90

95

95

150 ft.

70

90

100

100

175 ft.

70

90

100

100

200 ft.

70

90

100

100

225 ft.

75

95

*

*

250 ft.

75

95

*

*

275 ft.

75

95

*

*

300 ft.

75

95

*

*

* Do not use these control devices at distances greater

than 200 ft.

! WARNING

The compressor must provide adequate output,
and the plumbing between the compressor and
the point of attaching the respirator hose must
have sufficient capacity to supply the volume of
air at the pressure required (as stated in Section
4.2.2). Restricted air flow will cause discomfort to
the user, and may result in ingress of hazardous
and toxic dust, subjecting the user to health and
life threatening toxic poisoning and long term
respiratory disease and death.

5.0

OPERATION

! WARNING

With the respirator on, leave the blast area
immediately if any of the following conditions
occur:

• Any part of the respirator system becomes

damaged.

• Any air monitoring alarm is activated.
• Airflow into the respirator is reduced or

stops.

• Breathing becomes difficult.
• At the first sign of dizziness, nausea, fever,

illness or injury.

• Any contamination is noted by taste, smell

or vision inside the respirator.

• Vision becomes impaired.
• Any irritation is noted.

Содержание Apollo 60 HP

Страница 1: ...ou are using a Clemco Distributor Parts and Maintenance Guide refer to the orange warnings insert preceding the Index before continuing with the following instructions CLEMCO INDUSTRIES CORP One Cable...

Страница 2: ...i rator 1 1 2 OSHA requires the employer to establish a com prehensive respiratory protection program per regulations 29 CFR 1910 134 a b and 29 CFR 1926 103 to include the following 1 Program coordin...

Страница 3: ...sup plied air respirator equipment by blasting opera tors and all personnel within the work site area Leadpoisoningcancausedeath OSHAhasstated that the permissible exposure limit of lead is 50 microgr...

Страница 4: ...ntenance manuals for information on use and maintenance of these respirators 1 5 Special Use Limitations 1 5 1 Air pressure at the point of attachment the point of attachment is where the respirator s...

Страница 5: ...s conditions Constant Flow Connector CFC Provides non adjust able volume of supplied air within the cfm range required by OSHA Air Control Valve ACV Enables the user to a d j u s t the volume of suppl...

Страница 6: ...r lens by the window frame are up to five perforated outer lenses 3 2 2 Check that the inner lens is in place See Section 9 1 3 2 3 The perforated outer lenses are secured to the helmet by the window...

Страница 7: ...necessary safety and monitoring devices plus suitable in line air filters and purifying equipment to assure breathing air quality Refer ence OSHA Regulations 29 CFR 1910 134 d and 29 CFR 1926 103 f 4...

Страница 8: ...attached If the regulator is adjusted with static pressure no air flow pressure may drop below the required pressure when the respirator is connected and may result in low air flow Setting the pressur...

Страница 9: ...e positioned and maintained without any interference from items such as hair facial hair or shirt collars between the collar and user s neck 5 9 Pull the cape down to fully extend it and connect the f...

Страница 10: ...Try the helmet on for fit and readjust if necessary 6 2 9 Check that the chin strap is in place then reattach the cape onto the helmet following the instructions in Section 9 4 7 0 MAINTENANCE PROGRAM...

Страница 11: ...to circulate to dry condensation from the cape and from inside the helmet 7 5 2 Long term storage 7 5 2 1 After inspection cleaning and thorough drying and after necessary repairs are made the cape s...

Страница 12: ...eplacing Perforated Outer Lenses Figure 4 9 2 1 Up to five outer lenses can be installed at one time For maximum visibility install only enough lenses to last during a work period 9 2 2 Preparing lens...

Страница 13: ...tructions 9 6 Window Frame 9 6 1 The window frame must be replaced when it becomes difficult to maintain a seal or to keep the latch closed When replacing the window frame the acoustical foam inside t...

Страница 14: ...includes items 6 and 7 04398 6 Adaptor 3 8 hose to 3 8 pipe 00022 7 Union 3 8 hose to 3 8 hose 01020 8 Disconnect 1 4 female 00025 9 Adaptor 3 8 hose to 1 4 pipe 01019 10 Acoustical foam kit sides 04...

Отзывы: