Operation
3-16
750-437
Q Series Full Modulation
{400: SEt}
“400” flashing
press (
enter
) display shows:
{run}
press (
enter
) display shows:
{PH 12}
= stand by
Turn the burner switch ON, and the burner progresses through pre-ignition phases and trial for flame:
{Ph22}
= Fan motor on
{Ph24}
= Traveling to pre-purge position
{Ph30}
= Pre-purge countdown timer (30 sec)
{Ph36}
= Traveling to ignition position
{Ph38}
= Pre ignition Time
Progression stops at P0 setting:
{P0: : GG.r}
with "P0" blinking.
Press
(+)
to continue light off sequence:
{Ph40}
= 1st Safety Time (ignition transformer ON)
{Ph42}
= 1st Safety Time (ignition transformer OFF)
{Ph44}
= Interval 1
If light off fails return and repeat from step
d
.
If light off is successful, the controller halts the sequence and displays:
{P0: : GG.G}
“P0” is blinking
P0 may be adjusted further if desired. When satisfied with the P0 setting, press (+) to advance to P1.
G) Adjusting P1 through P9 points.
{P1: : GG.G}
“
P1
”
is blinking
Using the combustion analyzer, verify combustion for low-fire P1.
If adjustment is needed,
AIR-
Press and hold (VSD / F & A) and the display shows:
{1n: : SS.S}
with “SS.S” value flashing
Use (+) or (-) to adjust the setting. When the intended value is reached, release the keys.
GAS-
Press and hold (A) and the display shows:
{1A: : GG.G}
with “GG.G” value flashing
Use
(+)
or
(-)
to adjust the setting. When the intended value is reached, release the keys.
Содержание ProFire Q Series
Страница 2: ......
Страница 18: ...Introduction 1 8 750 437 Q Series Full Modulation...
Страница 28: ...Installation 2 10 750 437 Q Series Full Modulation...
Страница 50: ...Operation 3 22 750 437 Q Series Full Modulation...
Страница 82: ...Troubleshooting 6 24 750 437 Q Series Full Modulation...
Страница 87: ......
Страница 88: ......