Installation
2-6
750-437
Q Series Full Modulation
2.7 — Support Bracket Installation
Once the burner is installed, it must be supported by a suitable weight bearing surface. The burner is designed to
use the supplied support bracket kit number 880-06384-000. The bracket should be mounted to the burner
with the kit-supplied hardware.
A 3/4” NPS pipe, supplied by others, may then be cut to length and mounted so as to provide vertical support to
the burner.
FIGURE 2-6.
Support Bracket Installation
2.8 — Gas Piping
Gas service and house piping must supply the burner-required gas volume and pressure to the burner gas train
inlet. All piping must be in strict accordance with applicable codes, ordinances, and regulations of the supplying
utility. In the absence of other codes, piping should be in accordance with the following standards: “National
Fuel Gas Code” NFPA No. 54, ANSI No. Z 223.1 (for Canada, the Canadian Gas Association (CGA) B149 and
Canadian Standards Association (CSA) B140 codes shall prevail).
Full modulation gas train components upstream of the butterfly valve that are shipped loose should be mounted
by the installer as close to the burner as practical. Normally, the gas train is ordered to suit a particular code or
insurance regulation, such as Underwriters Laboratories Inc., CGA, or Factory Mutual.
Arrange gas piping to the burner so that the burner is accessible for servicing without requiring train disassembly.
The gas piping must be internally clean and free of foreign material. Before using in service, a leak test must be
performed.
750-00520-000
SUPPORT BRACKET
(SUPPLIED WITH BURNER)
PIPE, 3/4" NPS (TOE)
SUPPLIED BY OTHERS)
Содержание ProFire Q Series
Страница 2: ......
Страница 18: ...Introduction 1 8 750 437 Q Series Full Modulation...
Страница 28: ...Installation 2 10 750 437 Q Series Full Modulation...
Страница 50: ...Operation 3 22 750 437 Q Series Full Modulation...
Страница 82: ...Troubleshooting 6 24 750 437 Q Series Full Modulation...
Страница 87: ......
Страница 88: ......