CFH Startup Guide
8
Part No. 750-293
2 - STARTING THE BOILER
Ensure boiler has been filled with water (see above -
1.7 Filling Boiler
). The DEMAND switch should be in
the OFF position.
When the Control Circuit/Blower switch is turned ON, the Home page will appear on the CB Falcon display,
showing the boiler control icon. It may take a short time for the display/controller to initialize before the
Falcon icon appears.
If the Falcon icon does not appear, open the control panel and verify that the controller is receiving power.
The green ‘POWER’ LED should be lit (see
Figure 10
).
If the controller is powered on but still does not appear on the display, refer to manual. If unable to resolve
the problem, contact your CB representative.
2.1 Controller Configuration
The CB Falcon controller is factory pre-configured with default
parameter settings for the Model CFH. Prior to starting the boiler,
verify that the factor y default settings are correct for your
application. See the boiler operation manual (Chapter 4 -
Commissioning) for the parameter list and parameter change
procedure.
Changing the Setpoint
The default steam pressure setpoint should be changed at this time
to suit your application. Press the CB Falcon icon on the Home
page. The Overview screen will appear. On the bottom row of
screen buttons press <Operation> to access the Operation screen
(
Figure
11
).
Press the yellow highlighted setpoint display. A numeric keypad will appear. Press <Clear> to clear the
current value, enter the appropriate setting using the numeric keypad, and press <OK>.
Figure 10 Home Page; Falcon power indicator
HOME PAGE
POWER
Falcon
controller
icon
LED
Note:
The “Home” icon at the
upper lef t of the display
screen always returns to the
Home Page.
The “Back” icon at the upper
right displays the previous
screen.