CleaverBrooks ClearFire SFH Скачать руководство пользователя страница 8

CFH Startup Guide

8

Part No. 750-293

2 - STARTING THE BOILER

Ensure boiler has been filled with water (see above - 

1.7 Filling Boiler

). The DEMAND switch should be in

the OFF position.

When the Control Circuit/Blower switch is turned ON, the Home page will appear on the CB Falcon display,
showing the boiler control icon. It may take a short time for the display/controller to initialize before the
Falcon icon appears.

If the Falcon icon does not appear, open the control panel and verify that the controller is receiving power.
The green ‘POWER’ LED should be lit (see 

Figure 10

).

If the controller is powered on but still does not appear on the display, refer to manual. If unable to resolve
the problem, contact your CB representative.

2.1 Controller Configuration

The CB Falcon controller is factory pre-configured with default
parameter settings for the Model CFH. Prior to starting the boiler,
verify that the factor y default settings are correct for your
application. See the boiler operation manual (Chapter 4 -
Commissioning) for the parameter list and parameter change
procedure.

Changing the Setpoint

The default steam pressure setpoint should be changed at this time
to suit your application. Press the CB Falcon icon on the Home
page. The Overview screen will appear. On the bottom row of
screen buttons press <Operation> to access the Operation screen
(

Figure

 

11

).

Press the yellow highlighted setpoint display. A numeric keypad will appear. Press <Clear> to clear the
current value, enter the appropriate setting using the numeric keypad, and press <OK>.

Figure 10  Home Page; Falcon power indicator

HOME PAGE

POWER

Falcon

controller

icon

LED

Note:

The “Home” icon at the
upper lef t of the display
screen always returns to the
Home Page.

     

The “Back” icon at the upper
right displays the previous
screen.

Содержание ClearFire SFH

Страница 1: ...www cleaverbrooks com ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750 293...

Страница 2: ...essure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa DANGER WARNING Should overheating occur or the gas supply valve fail to shut off do not turn off or disconnect the electric...

Страница 3: ...voltage ignition transformers Control panel must be connected to earth ground For electrical wiring requirements see wiring diagram provided with the boiler or in the CFH manual Figure 1 CFH Connecti...

Страница 4: ...re to be connected to the ClearFire boiler Refer to flue piping manufacturer for proper installation and sealing instructions See also Chapter 3 in the CFH Operation and Maintenance manual 1 4 Boiler...

Страница 5: ...in power 115 VAC single phase 60Hz and any remote wiring should be brought to the left side of the control panel and terminated at the appropriate terminals provided Controls for the boiler feed pump...

Страница 6: ...e Figure 5 include the following Combustion Air Proving Switch Low Gas Pressure Switch High Gas Pressure Switch Dual Safety Shut off Valve SSOV Depress all manual reset buttons for all controls prior...

Страница 7: ...not close the vent valve until water is visible in the gauge glass The feed pump will shut off when water reaches the Pump Off probe level Check to ensure that no leaks appear at any pipe connections...

Страница 8: ...pre configured with default parameter settings for the Model CFH Prior to starting the boiler verify that the factory default settings are correct for your application See the boiler operation manual...

Страница 9: ...igure 12 Operation screen 2 3 4 To change the steam pressure setpoint 1 Press the yellow highlighted setpoint display window 2 Clear the current value 3 Enter the desired value 4 Press OK 1 Note Some...

Страница 10: ...ble and attempt to start the burner The CB Falcon should lock out indicating Lockout 109 Ignition Failure Reconnect flame rod cable after test The CB Falcon requires a manual reset to resume operation...

Страница 11: ...manual for boil out procedure 5 LOCKOUTS HOLDS AND ALERTS To assist in monitoring boiler operation the CB Falcon control system employs messages of three types Lockouts Holds and Alerts Lockouts and...

Страница 12: ...Figure 15 Press this banner to access the Alert or Lockout History where a list of the most recently occurring Alerts Lockouts can be viewed To obtain more information for a particular message press t...

Страница 13: ...CFH Startup Guide Part No 750 293 13 Figure 16 CFH Wiring Diagram...

Отзывы: