CFH Startup Guide

Part No. 750-293

11

If any of the following conditions occur:

• Loss of flame
• Excessive or unusual noise
• Flame appears irregular when viewed through sight glass
• Frequent low water shutdowns

Cease boiler operation. See the Troubleshooting section in the CFH manual or consult your authorized CB
representative.

Repeated nuisance low water shutdowns may indicate a problem with the boiler feed system and/or water
level controls.

4 - POST STARTUP

• Review 

Chapter 4 - Commissioning 

in the CFH manual. Ensure all safety checks have been performed 

according to instructions.

• Set high gas pressure switch to 50% higher than operating gas pressure at low fire. Set low gas pressure 

switch to 50% lower than operating gas pressure at low fire.

• Check the draft on the outlet stack and compare to acceptable limits (-0.25 to +0.25 inches WC). 

Operating outside of acceptable limits could result in light off and flame failure problems.

• Verify gas pressure remains within limits shown in Table 1.

• A new boiler should be cleaned by boil-out prior to being placed into service. See Chapter 4 of the CFH 

manual for boil-out procedure.

5 - LOCKOUTS, HOLDS, AND ALERTS

To assist in monitoring boiler operation, the CB Falcon control system employs messages of three types:

Lockouts

,

 Holds

,

 

and

 Alerts

.

Lockouts

 and 

Holds

 indicate interruptions in boiler operation, whether occurring as part of the normal 

operating sequence or due to an abnormal condition. Lockouts require a manual reset to continue operation, 
while Holds do not. A Hold will automatically clear when the hold condition is removed or satisfied. 

The most recent Lockouts are stored in CB Falcon memory and may be accessed through the Lockout
History. Holds are not logged in memory.

Note:

 

Before attempting to restart the boiler after a Lockout, identify and correct the Lockout condition.

Notice

The CFH has been factory tested at 1000’ ASL and tuned for 5-6%
excess O

2

. To ensure optimum combustion throughout the firing

range, the O

2

% should be verified and if necessary adjusted to the

proper levels. This procedure involves manually firing the burner
while using a combustion analyzer to monitor O

2

%. Low and high

fire adjustments are made at the main gas valve. See the CFH
Operation and Maintenance manual for a detailed procedure.

Note:

 If an alarm or lockout occurs 

during startup or operation, see the 
boiler Operation and Maintenance 
manual

Содержание ClearFire SFH

Страница 1: ...www cleaverbrooks com ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750 293...

Страница 2: ...essure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa DANGER WARNING Should overheating occur or the gas supply valve fail to shut off do not turn off or disconnect the electric...

Страница 3: ...voltage ignition transformers Control panel must be connected to earth ground For electrical wiring requirements see wiring diagram provided with the boiler or in the CFH manual Figure 1 CFH Connecti...

Страница 4: ...re to be connected to the ClearFire boiler Refer to flue piping manufacturer for proper installation and sealing instructions See also Chapter 3 in the CFH Operation and Maintenance manual 1 4 Boiler...

Страница 5: ...in power 115 VAC single phase 60Hz and any remote wiring should be brought to the left side of the control panel and terminated at the appropriate terminals provided Controls for the boiler feed pump...

Страница 6: ...e Figure 5 include the following Combustion Air Proving Switch Low Gas Pressure Switch High Gas Pressure Switch Dual Safety Shut off Valve SSOV Depress all manual reset buttons for all controls prior...

Страница 7: ...not close the vent valve until water is visible in the gauge glass The feed pump will shut off when water reaches the Pump Off probe level Check to ensure that no leaks appear at any pipe connections...

Страница 8: ...pre configured with default parameter settings for the Model CFH Prior to starting the boiler verify that the factory default settings are correct for your application See the boiler operation manual...

Страница 9: ...igure 12 Operation screen 2 3 4 To change the steam pressure setpoint 1 Press the yellow highlighted setpoint display window 2 Clear the current value 3 Enter the desired value 4 Press OK 1 Note Some...

Страница 10: ...ble and attempt to start the burner The CB Falcon should lock out indicating Lockout 109 Ignition Failure Reconnect flame rod cable after test The CB Falcon requires a manual reset to resume operation...

Страница 11: ...manual for boil out procedure 5 LOCKOUTS HOLDS AND ALERTS To assist in monitoring boiler operation the CB Falcon control system employs messages of three types Lockouts Holds and Alerts Lockouts and...

Страница 12: ...Figure 15 Press this banner to access the Alert or Lockout History where a list of the most recently occurring Alerts Lockouts can be viewed To obtain more information for a particular message press t...

Страница 13: ...CFH Startup Guide Part No 750 293 13 Figure 16 CFH Wiring Diagram...

Отзывы: