Inspection and Maintenance
5-10
750-392
CBEX-DE
5.10 — Motorized Gas Valve
The motorized gas valve operating mechanism contains no user serviceable parts. An inoperative actuator must
be replaced.
5.11 — Solenoid Valves
Foreign matter between the valve seat and seat disc can cause leakage. Valves are readily disassembled; how-
ever, care must be used during disassembly to be sure that internal parts are not damaged during the removal
and that reassembly is in proper order.
A low hum or buzzing will normally be audible when the coil is energized. If the valve develops a loud buzzing or
chattering noise, check for proper voltage and clean the plunger assembly and interior plunger tube thoroughly.
Do not use any oil. Be sure that the plunger tube and solenoid are tight when reassembled. Take care not to nick,
dent, or damage the plunger tube.
Coils may be replaced without removing the valve from the line.
Check coil position and make sure that any insulating washers or retaining springs are reinstalled in proper order.
5.12 — Air Control Damper
The burner air control damper should be checked for free movement as a part of the monthly inspection. With
the burner off and the actuator removed, the air control damper should rotate freely through its entire range of
movement. Any resistance to movement or excessive play in the support bearing should be investigated and cor-
rected before the burner is put back in operation.
Ensure the gears are fully engaged throughout the entire damper rotational range.
Be sure to turn off power to the valve in order to avoid electrical shock. Failure to follow these instructions could
result in serious injury or death.
!
Warning
Содержание CBEX-DE
Страница 1: ...CBEX DE Dryback Elite Boiler 250 800 HP Operation and Maintenance 750 392 10 2019 ...
Страница 54: ...Preparations for Startup 3 22 750 392 CBEX DE ...
Страница 74: ...Startup and Operation 4 20 750 392 CBEX DE ...
Страница 104: ...Inspection and Maintenance 5 30 750 392 CBEX DE ...
Страница 122: ...Parts 6 18 750 392 CBEX DE 6 11 Temperature Controls Hot Water ...
Страница 124: ......