background image

CB780/CB784 RELAY MODULES

7

32-00207—01

changes but avoid the occurrence of 

nuisance

 shutdown 

events. Signal conditioning is applied to line voltage 
inputs to verify proper operation in the presence of 

normal

 

electrical line noise such as transient high voltage spikes 
or short periods of line dropout. Signal conditioning is 
tolerant of synchronous noise (line noise events that occur 
at the same time during each line cycle).

Dynamic Ampli-Check™

Dynamic AMPLI-CHECK™ circuitry tests the flame signal 
amplifier during burner operation and shuts down the
CB780/CB784 if the flame amplifier fails. 

Dynamic Flame Amplifier and 
Shutter Check

Self-checking circuitry tests all electronic components in 
the flame detection system and amplifier 10 to 12 times 
per minute and shuts down the CB780/CB784 if the 
detection system fails. 

Dynamic Input Check

All system input circuits are examined to verify that the 
CB780/CB784 is capable of recognizing the true status of 
external controls, limits and interlocks. If any input fails 
this test, a safety shutdown occurs and the fault is 
annunciated. 

Dynamic Safety Relay Test

Checks the ability of the dynamic safety relay contacts to 
open and close. It also verifies that the safety critical loads, 
terminals 8, 9, 10 and 21, can be de-energized, as 
required, by the Dynamic Self-Check logic.

Dynamic Self-Check Safety Circuit

The microcomputer tests itself and related hardware while 
at the same time the safety relay system tests the 
microcomputer operation. If a microcomputer or safety 
relay failure occurs and does not allow proper execution of 
the 
self-check routine, safety shutdown will occur and all 
safety critical loads will be de-energized.

Expanded Safe-Start Check

The conventional safe-start check, which prevents burner 
start-up if flame is indicated at start-up, is expanded to 
include a flame signal check during STANDBY, a 
preignition interlock check, an interlock check, and a 
safety critical load check. 

High Fire Purge and Low Fire Start 
Switch Tests

High Fire Purge Switch Test 

examines the Purge Position 

Interlock Switch at the moment the firing rate motor is 
commanded to the high fire position. If the switch is 
bypassed, welded or otherwise closed prematurely, the 
system will automatically add 30 seconds to allow 
additional drive time for the firing rate motor to reach or 

near the open position before starting the purge timing; 
otherwise, purge timing starts when the High Fire Switch 
is closed. This switch will also cause a hold (four minutes, 
fifteen seconds) condition when the switch is open before 
purge or opens during purge. The 
CB780/CB784 will lockout and annunciate an alarm if the 
switch fails to close within the hold time period. 

Low Fire Start Switch Test

 examines the Low Fire Start 

Switch at the moment PREPURGE is completed. If the 
switch is bypassed, welded or otherwise prematurely 
closed, the system automatically adds 30 seconds to allow 
the firing rate motor additional time to reach or near the 
low fire start position before ignition trials; otherwise, 
ignition trials start after the Low Fire Switch closes. The 
test also is used to prove that the firing rate motor is at low 
fire position throughout the ignition trial period. This 
switch will also cause a hold (four minutes, fifteen 
seconds) condition if the switch opens after purging is 
complete. The CB780/CB784 will lockout and annunciate 
an alarm if the switch fails to close within the hold time 
period. 

Mandatory Purge

If lockout occurs after the initiation of ignition trials, (or at 
anytime during a sequence when the fuel valves may have 
been energized), a mandatory POSTPURGE period is 
imposed. 

Off Cycle (STANDBY or PREPURGE) 
Flame Signal Check

The flame detection subsystem (flame detector and 
amplifier) is monitored during STANDBY. If a flame 
simulating condition or an actual flame exists, a system 
hold occurs and start-up is prevented. If the flame signal 
exists at any time after the first 40 seconds of STANDBY, a 
safety shutdown will occur and be annunciated. A shutter-
check amplifier and self-checking detector are energized 
for the first 40 seconds during STANDBY and the last two 
seconds before exiting STANDBY. If a flame exists, a safety 
shutdown occurs. An 
AMPLI-CHECK™ Amplifier is energized continually 
through STANDBY and PREPURGE to detect any 
possibility of a runaway detector or a flame. If either 
situation happens, a safety shutdown occurs. A standard 
amplifier is energized continually through STANDBY and 
PREPURGE. If either situation happens, a safety shutdown 
occurs. 

Preignition Output Circuit Check

At the end of PREPURGE, the Dynamic Safety Relay 
operation is checked. Also, all safety critical loads, 
terminals 8, 9, 10 and 21 are checked to verify the 
terminals are not powered. If the Dynamic Safety Relay 
operation is faulty, or if any of the safety critical loads are 
powered, safety shutdown occurs and is annunciated. 

Tamper-Resistant Timing and Logic

Safety and logic timings are inaccessible and cannot be 
altered or defeated. 

Содержание CB780

Страница 1: ...B784 include automatic burner sequencing flame supervision system status indication system or self diagnostics and troubleshooting FEATURES Safety features Interlock check Closed loop logic test Dynam...

Страница 2: ...t history of six most recent faults Cycles of operation at time of fault Expanded annunciator data at time of fault Fault message and code Hours of operation at time of fault Sequence status at time o...

Страница 3: ...ing 40 F to 140 F 40 C to 40 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 RH continuous noncondensing Vibration 0 5G environment Dimensions Refer to Fig 1 and 2 Weight CB780 CB784 1 pound 10 ounce...

Страница 4: ...AF IRI acceptable Federal Communications Commission Part 15 Class B Emissions Mounting 833 2725 for panel mount Required Components CB780 120 Vac 50 60 Hz 833 2718 CB784 120 Vac 50 60 Hz 833 2720 Plu...

Страница 5: ...AIN ALARM RESET 5 127 5 127 M23943C REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 5 1 4 133 BACK ENTER Edit 2 1 32 52 BURNER CONTROL 29 32 23 19 32 15 1 1 4 32 1 1 32 26 5 32 4 5 16 8 M23388C 1 2 13 7 16 1...

Страница 6: ...s b Lockout Interlock opens c Ignition pilot valve intermittent pilot valve ter minal is not energized d Early Spark Termination terminal is energized after five seconds e No flame is present at end o...

Страница 7: ...rwise purge timing starts when the High Fire Switch is closed This switch will also cause a hold four minutes fifteen seconds condition when the switch is open before purge or opens during purge The C...

Страница 8: ...Interlock opens during the first ten seconds the purge timer will be reset This provides a continuous PURGE to occur without interruption before the Pilot Flame Establishing Period If a Lockout Inter...

Страница 9: ...recommended Any other position decreases the maximum ambient temperature rating 2 The 833 2725 Wiring Subbase can be mounted directly in the control cabinet Be sure to allow ade quate clearance for se...

Страница 10: ...Fig 6 Internal block diagram of the CB780 CB784 see Fig 7 8 9 or 10 for detailed wiring instructions CONFIGURATION JUMPERS MICROCOMPUTER RESET PUSHBUTTON RUN TEST SWITCH STATUS LEDs PLUG IN PURGE TIME...

Страница 11: ...ignition transformer wires in the same conduit with the flame detection wiring 2 Do not route scanner wires in conduit with line voltage circuits 3 Enclose scanner wires without armor cable in metal...

Страница 12: ...0 SEC INTERRUPTED PILOT IGNITION PREIGNITION INTERLOCK SERIES 90 FIRING RATE MOTOR SERIES 90 CONTROLLER 817 1742 INFRARED LEAD SULFIDE FLAME DETECTOR 817 1743 ULTRAVIOLET FLAME DETECTOR 817 1121 ULTRA...

Страница 13: ...80 CB 784 RELAY MODULE 13 VDC POWER SUPPLY 833 2727 REMOTE KEYBOARD DISPLAY MODULE THREE WIRE SHIELDED CABLE MAY BE REQUIRED TWO 120 OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEE...

Страница 14: ...ther than a hinge action 4 Mount the CB780 CB784 by aligning the four L shaped corner guides and knife blade terminals with the bifurcated contacts on the wiring subbase and tightening the two screws...

Страница 15: ...e Keyboard Dis play Module with the two mating slots on the CB780 CB784 see Fig 13 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the lower cor ners of th...

Страница 16: ...gnal Amplifier 1 Disconnect power supply before beginning installa tion to prevent electrical shock and equipment dam age More than one disconnect may be involved 2 Align the amplifier circuit board e...

Страница 17: ...B780 CB784 provides a PREPURGE timing selectable from 30 seconds to 2 1 2 minutes with power applied and the CB780 CB784 operating control indicating a call for heat Running Interlocks Preignition Int...

Страница 18: ...ergized for early spark termination 4 Main Flame Establishing Period MFEP a The CB780 CB784 has a selectable ten second or fifteen second MFEP After the Ignition Trials and with the presence of flame...

Страница 19: ...it or a lockout message is available The CB780 CB784 LEDs provide positive visual indication of the program sequence POWER PILOT FLAME MAIN and ALARM Fig 18 Keyboard Display Module and sequence status...

Страница 20: ...DELAY Low Fire Jumprd POWER PILOT FLAME MAIN AND ALARM PURGE HOLD F G Flame Detected POWER PILOT FLAME MAIN AND ALARM PURGE HOLD Low Fire Switch POWER PILOT FLAME MAIN AND ALARM PILOT IGN minutes sec...

Страница 21: ...instantaneously switches the display from a second line selectable message to second line preempted message The sixty sec ond timeout function also can be used for this task The MODE pushbutton will...

Страница 22: ...ion PILOT IGN 00 05 Fault History M7402C PILOT IGN 00 10 H1 Fault Cycle 174 SCROLL MODE SAVE SCROLL MODE SAVE BURNER CONTROL BURNER CONTROL LOCKOUT 17 MFEP Main Valve 0 M7403D LOCKOUT 17 MFEP Main Fla...

Страница 23: ...t Hours nnnnn H2 Fault Code nnn H2 fault message H2 sequence message H2 second line msg H2 Fault Cycle nnnnn H3 Fault Hours nnnnn H3 Fault Code nnn H3 fault message H3 sequence message H3 second line...

Страница 24: ...RM78nnx DI Device Suffix nnnn DI Run Test Sw RUN or TEST DI Operating Control OperControl 1 or 0 DI Interlock 1 or 0 DI Pilot Valve 1 or 0 DI Main Valve 1 or 0 DI Ignition 1 or 0 DI Low Fire Sw 1 or 0...

Страница 25: ...nored during PFEP for the CB780 CB784 if terminals 8 and 9 or 9 and 21 are jumpered 5 During RUN the Run Test Switch when placed in the TEST position will drive the firing rate motor to the Low Fire p...

Страница 26: ...ernal surge pro tectors will break down and conduct a current This could cause the CB780 CB784 to fail the dielectric test or possibly destroy the internal lightning and high current protection Equipm...

Страница 27: ...nsformer is con nected to terminal 8 2 Automatic pilot valve opens if connected to terminal 8 NOTE Refer to wiring diagram of system being tested 1 Watch for spark or listen for buzz a Ignition electr...

Страница 28: ...on and CB780 CB784 System Annunciation Diagnostics and Troubleshooting Bulletin Number CB 7803 2 Repeat ALL required Checkout tests after all adjustments are made ALL tests must be satisfied with the...

Страница 29: ...1 Use one megohm volt meter with a 0 to 10 Vdc capability 2 Set the one megohm volt meter to the 0 to 10 Vdc range 3 Insert the positive red probe into the jack of the flame amplifier Insert the negat...

Страница 30: ...nals 8 10 or 21 refer to the appropriate wiring diagram to determine the proper terminal Disconnect the leadwire to the pilot valve if it is connected to the same terminal c Close the master switch to...

Страница 31: ...ten sec ond INITIATE sequence 5 Let the sequence advance through PREPURGE Ignition spark should occur after PREPURGE period Listen for the click of the first stage fuel solenoid valve s 6 Let the pro...

Страница 32: ...e exact point the FLAME LED light goes out 9 Increase the pilot pressure immediately until the FLAME LED comes on and then turn it down slowly to obtain a pressure reading just above the dropout point...

Страница 33: ...equipment Operating Manual Continue adjustments until hot refractory hold in is eliminated Ultraviolet Sensor Ignition Spark Response Test All Ultraviolet Detectors Test to make certain that the ignit...

Страница 34: ...Fail fault will be displayed on the KDM Fault code 17 will be displayed to denote the fault g Safety shutdown will occur 7 Opening a Preignition Interlock after the first five seconds of POSTPURGE a...

Страница 35: ...ERVICE NOTE If the Keyboard Display Module is scrambled remove and reinstall the Keyboard Display Module and reset the CB780 CB784 Relay Module SERVICE NOTE Use the access slots on the sides of the Wi...

Страница 36: ...ing of device physically secure Physical protection of the device is applied via Run Test switch label seal It is intended to prevent and detect unauthorized access Modbus DDL Interface security Any c...

Отзывы: