CleaverBrooks CB780 Скачать руководство пользователя страница 33

CB780/CB784 RELAY MODULES

33

32-00207—01

Hot Refractory Hold-in Test (All 
Infrared Detectors)

Test to make certain hot refractory will not delay the flame 
detection system response to a flameout. This condition 
can delay response to flame failure and also can prevent a 
system restart as long as hot refractory is detected. 

Infrared (lead sulfide) detectors can respond to infrared 
rays emitted by a hot refractory, even when the refractory 
has visibly ceased to glow. Infrared radiation from a hot 
refractory is steady, but radiation from a flame has a 
flickering characteristic. The infrared detection system 
responds only to flickering infrared radiation; it can reject 
a steady signal from hot refractory. The refractory steady 
signal can be made to fluctuate if it is reflected, bent or 
blocked by smoke or fuel mist within the combustion 
chamber. Be careful when applying an infrared system to 
verify its response to flame only. 

To check infrared (lead sulfide) detectors for hot refractory 
hold-in, operate the burner until the refractory reaches its 
maximum temperature. If the installation has a multi-fuel 
burner, burn the heavier fuel that is most likely to reflect, 
bend or obscure the hot refractory steady infrared 
radiation. When the maximum refractory temperature is 
reached, close all manual fuel shutoff valve(s), or open the 
electrical circuits of all automatic fuel valve(s). Visually 
observe when the burner flame or FLAME LED goes out. If 
this takes more than three seconds, the infrared detector 
is sensing hot refractory. Immediately terminate the firing 
cycle. (Lower the set point to the operating controller, or 
set the Burner Switch to OFF. Do not open the master 
switch.)

NOTE:

Some burners continue to purge oil lines between 
the valve(s) and nozzle(s) even though the fuel 
valve(s) are closed. Terminating the firing cycle 
(instead of opening the master switch) will allow 
purging the combustion chamber. This will 
reduce a buildup of fuel vapors in the combustion 
chamber caused by oil line purging. 

If the detector is sensing hot refractory, the condition 
must be corrected. Add an orifice plate in front of the cell 
to restrict the viewing area of the detector. If this does not 
correct the problem, resight the detector at a cooler, more 
distant part of the combustion chamber. While resighting 
the detector, be aware that it must also properly sight the 
flame. For an infrared detector, try lengthening the sight 
pipe or decreasing the pipe size (diameter). For details, 
refer to the detector Instructions and the equipment 
Operating Manual. Continue adjustments until hot 
refractory hold-in is eliminated. 

Ultraviolet Sensor, Ignition Spark 
Response Test (All Ultraviolet 
Detectors)

Test to make certain that the ignition spark is not 
actuating the FLAME LED. 

1.

Close the pilot and main burner manual fuel shut-off 
valve(s).

2.

Start the burner and use the Run/Test Switch to stop 
the sequence in the PILOT IGN period. Ignition spark 
should occur, but the flame signal should not be 
more than 0.5 Vdc.

3.

If the flame signal is higher than 0.5 Vdc and the 
FLAME LED does come on, consult the equipment 
operating manual and resight the detector farther 
out from the spark, or away from possible reflection. 
It may be necessary to construct a barrier to block 
the ignition spark from the detector view. Continue 
adjustments until the flame signal due to ignition 
spark is less than 0.5 Vdc.

Response to Other Ultraviolet 
Sources

Some sources of artificial light, such as incandescent or 
fluorescent bulbs, mercury sodium vapor lamps and 
daylight, produce small amounts of ultraviolet radiation. 
Under certain conditions, an ultraviolet detector will 
respond to these sources as if it is sensing a flame. To 
check for proper detector operation, check the Flame 
Failure Response Time (FFRT) and conduct Safety 
Shutdown Tests under all operating conditions. 

Flame Signal With Hot Combustion 
Chamber (All Installations)

With all initial start-up tests and burner adjustments 
completed, operate the burner until the combustion 
chamber is at the maximum expected temperature. 
Observe the equipment manufacturer warm-up 
instructions. Recycle the burner under these hot 
conditions and measure the flame signal. Check the pilot 
alone, the main burner flame alone, and both together 
(unless monitoring only the main burner flame when 
using DSI). Check the signal at both High and Low Firing 
Rate positions and while modulating, if applicable. 

If the flame signal is too low or unsteady, check the flame 
detector temperature. Relocate the detector if the 
temperature is too high. If necessary, realign the sighting 
to obtain the proper signal and response time. If the 
response time is still too slow, replace the Plug-in Flame 
Signal Amplifier. If the detector is relocated or resighted, or 
the amplifier is replaced, repeat all required Checkout 
tests.Check the FFRT of the Flame Amplifier.  Lower the set 
point of the operating controller and observe the time it 
takes for the burner flame to go out. This should be within 
3 seconds maximum.

Safety Shutdown Tests (All 
Installations)

Perform these tests at the end of Checkout, after all other 
tests have been completed. If used, the external alarm 
should turn on. Press the CB780/CB784 reset pushbutton 
to restart the system. 

Содержание CB780

Страница 1: ...B784 include automatic burner sequencing flame supervision system status indication system or self diagnostics and troubleshooting FEATURES Safety features Interlock check Closed loop logic test Dynam...

Страница 2: ...t history of six most recent faults Cycles of operation at time of fault Expanded annunciator data at time of fault Fault message and code Hours of operation at time of fault Sequence status at time o...

Страница 3: ...ing 40 F to 140 F 40 C to 40 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 RH continuous noncondensing Vibration 0 5G environment Dimensions Refer to Fig 1 and 2 Weight CB780 CB784 1 pound 10 ounce...

Страница 4: ...AF IRI acceptable Federal Communications Commission Part 15 Class B Emissions Mounting 833 2725 for panel mount Required Components CB780 120 Vac 50 60 Hz 833 2718 CB784 120 Vac 50 60 Hz 833 2720 Plu...

Страница 5: ...AIN ALARM RESET 5 127 5 127 M23943C REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 5 1 4 133 BACK ENTER Edit 2 1 32 52 BURNER CONTROL 29 32 23 19 32 15 1 1 4 32 1 1 32 26 5 32 4 5 16 8 M23388C 1 2 13 7 16 1...

Страница 6: ...s b Lockout Interlock opens c Ignition pilot valve intermittent pilot valve ter minal is not energized d Early Spark Termination terminal is energized after five seconds e No flame is present at end o...

Страница 7: ...rwise purge timing starts when the High Fire Switch is closed This switch will also cause a hold four minutes fifteen seconds condition when the switch is open before purge or opens during purge The C...

Страница 8: ...Interlock opens during the first ten seconds the purge timer will be reset This provides a continuous PURGE to occur without interruption before the Pilot Flame Establishing Period If a Lockout Inter...

Страница 9: ...recommended Any other position decreases the maximum ambient temperature rating 2 The 833 2725 Wiring Subbase can be mounted directly in the control cabinet Be sure to allow ade quate clearance for se...

Страница 10: ...Fig 6 Internal block diagram of the CB780 CB784 see Fig 7 8 9 or 10 for detailed wiring instructions CONFIGURATION JUMPERS MICROCOMPUTER RESET PUSHBUTTON RUN TEST SWITCH STATUS LEDs PLUG IN PURGE TIME...

Страница 11: ...ignition transformer wires in the same conduit with the flame detection wiring 2 Do not route scanner wires in conduit with line voltage circuits 3 Enclose scanner wires without armor cable in metal...

Страница 12: ...0 SEC INTERRUPTED PILOT IGNITION PREIGNITION INTERLOCK SERIES 90 FIRING RATE MOTOR SERIES 90 CONTROLLER 817 1742 INFRARED LEAD SULFIDE FLAME DETECTOR 817 1743 ULTRAVIOLET FLAME DETECTOR 817 1121 ULTRA...

Страница 13: ...80 CB 784 RELAY MODULE 13 VDC POWER SUPPLY 833 2727 REMOTE KEYBOARD DISPLAY MODULE THREE WIRE SHIELDED CABLE MAY BE REQUIRED TWO 120 OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEE...

Страница 14: ...ther than a hinge action 4 Mount the CB780 CB784 by aligning the four L shaped corner guides and knife blade terminals with the bifurcated contacts on the wiring subbase and tightening the two screws...

Страница 15: ...e Keyboard Dis play Module with the two mating slots on the CB780 CB784 see Fig 13 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the lower cor ners of th...

Страница 16: ...gnal Amplifier 1 Disconnect power supply before beginning installa tion to prevent electrical shock and equipment dam age More than one disconnect may be involved 2 Align the amplifier circuit board e...

Страница 17: ...B780 CB784 provides a PREPURGE timing selectable from 30 seconds to 2 1 2 minutes with power applied and the CB780 CB784 operating control indicating a call for heat Running Interlocks Preignition Int...

Страница 18: ...ergized for early spark termination 4 Main Flame Establishing Period MFEP a The CB780 CB784 has a selectable ten second or fifteen second MFEP After the Ignition Trials and with the presence of flame...

Страница 19: ...it or a lockout message is available The CB780 CB784 LEDs provide positive visual indication of the program sequence POWER PILOT FLAME MAIN and ALARM Fig 18 Keyboard Display Module and sequence status...

Страница 20: ...DELAY Low Fire Jumprd POWER PILOT FLAME MAIN AND ALARM PURGE HOLD F G Flame Detected POWER PILOT FLAME MAIN AND ALARM PURGE HOLD Low Fire Switch POWER PILOT FLAME MAIN AND ALARM PILOT IGN minutes sec...

Страница 21: ...instantaneously switches the display from a second line selectable message to second line preempted message The sixty sec ond timeout function also can be used for this task The MODE pushbutton will...

Страница 22: ...ion PILOT IGN 00 05 Fault History M7402C PILOT IGN 00 10 H1 Fault Cycle 174 SCROLL MODE SAVE SCROLL MODE SAVE BURNER CONTROL BURNER CONTROL LOCKOUT 17 MFEP Main Valve 0 M7403D LOCKOUT 17 MFEP Main Fla...

Страница 23: ...t Hours nnnnn H2 Fault Code nnn H2 fault message H2 sequence message H2 second line msg H2 Fault Cycle nnnnn H3 Fault Hours nnnnn H3 Fault Code nnn H3 fault message H3 sequence message H3 second line...

Страница 24: ...RM78nnx DI Device Suffix nnnn DI Run Test Sw RUN or TEST DI Operating Control OperControl 1 or 0 DI Interlock 1 or 0 DI Pilot Valve 1 or 0 DI Main Valve 1 or 0 DI Ignition 1 or 0 DI Low Fire Sw 1 or 0...

Страница 25: ...nored during PFEP for the CB780 CB784 if terminals 8 and 9 or 9 and 21 are jumpered 5 During RUN the Run Test Switch when placed in the TEST position will drive the firing rate motor to the Low Fire p...

Страница 26: ...ernal surge pro tectors will break down and conduct a current This could cause the CB780 CB784 to fail the dielectric test or possibly destroy the internal lightning and high current protection Equipm...

Страница 27: ...nsformer is con nected to terminal 8 2 Automatic pilot valve opens if connected to terminal 8 NOTE Refer to wiring diagram of system being tested 1 Watch for spark or listen for buzz a Ignition electr...

Страница 28: ...on and CB780 CB784 System Annunciation Diagnostics and Troubleshooting Bulletin Number CB 7803 2 Repeat ALL required Checkout tests after all adjustments are made ALL tests must be satisfied with the...

Страница 29: ...1 Use one megohm volt meter with a 0 to 10 Vdc capability 2 Set the one megohm volt meter to the 0 to 10 Vdc range 3 Insert the positive red probe into the jack of the flame amplifier Insert the negat...

Страница 30: ...nals 8 10 or 21 refer to the appropriate wiring diagram to determine the proper terminal Disconnect the leadwire to the pilot valve if it is connected to the same terminal c Close the master switch to...

Страница 31: ...ten sec ond INITIATE sequence 5 Let the sequence advance through PREPURGE Ignition spark should occur after PREPURGE period Listen for the click of the first stage fuel solenoid valve s 6 Let the pro...

Страница 32: ...e exact point the FLAME LED light goes out 9 Increase the pilot pressure immediately until the FLAME LED comes on and then turn it down slowly to obtain a pressure reading just above the dropout point...

Страница 33: ...equipment Operating Manual Continue adjustments until hot refractory hold in is eliminated Ultraviolet Sensor Ignition Spark Response Test All Ultraviolet Detectors Test to make certain that the ignit...

Страница 34: ...Fail fault will be displayed on the KDM Fault code 17 will be displayed to denote the fault g Safety shutdown will occur 7 Opening a Preignition Interlock after the first five seconds of POSTPURGE a...

Страница 35: ...ERVICE NOTE If the Keyboard Display Module is scrambled remove and reinstall the Keyboard Display Module and reset the CB780 CB784 Relay Module SERVICE NOTE Use the access slots on the sides of the Wi...

Страница 36: ...ing of device physically secure Physical protection of the device is applied via Run Test switch label seal It is intended to prevent and detect unauthorized access Modbus DDL Interface security Any c...

Отзывы: