Operator's Manual: Models CB-3500 & CB-5000
4-20
Installing the Stack (continued)
Figure 4M - Installation of "Class A" Stack Through Sidewall
"CLASS A" STACK CAP
NON-RESTRICTIVE TYPE TO ALLOW
FREE FLOW OF THE STACK GASES
-.02 W.C. DRAFT
OVERFIRE IS
ESSENTIAL FOR
PROPER FURNACE
OPERATION.
SEE SECTION 8.
SINGLE WALL
STACK
MIN. 24
GAUGE
BAROMETRIC
DAMPER
"CLASS A" STACK
PENETRATION AND
CLEAN-OUT TEE
10 FT. (3 M)
3 FT
. (90 cm)
NOTE: THE LAST STACK SECTION SHALL EXTEND AT
LEAST 3 FEET (90 CM) HIGHER THAN ANY RIDGE,
PARAPET, WALL, OR ROOF STRUCTURE WITHIN
10 FEET (3 M) OF IT.
10 FT
. (3 M) MINIMUM
VER
TIC
AL ST
ACK HEIGHT
"CLASS A
" ST
ACK C
OMPONENT
S
INSULA
TED ST
ACK
WITH A ST
AINLESS STEEL LINER
I88365-B
FOR MORE DRAFT
TURN
WEIGHT
AIR OIL