Operator's Manual: Models CB-3500 & CB-5000
6-3
Initial Adjustments for CB-3500
Maximum Input = 350,000 BTUH @ 2.5 GPH with CB525-S2 Burner
Oil Type Oil PSI / Flame Length
Air PSI
Air Band
Nozzle
#2 Fuel Oil*
6.5 &
check flame length
12-18
3/4"
9-5
#4 and #5 Fuel Oils
6.5 &
check flame length
12-18
3/4"
9-5
Used Crankcase Oil
7.0 &
check flame length
12-18
3/4"
9-5
Used ATF
7.0 &
check flame length
12-18
3/4"
9-5
Used Hydraulic Oil
7.0 &
check flame length
12-18
3/4"
9-5
Initial Adjustments for CB-5000
Maximum Input = 500,000 BTUH @ 3.6 GPH with CB550-S2 Burner
Oil Type Oil PSI / Flame Length
Air PSI
Air Band
Nozzle
#2 Fuel Oil*
3.5 &
check flame length
12-18
1/4"
9-11
#4 and #5 Fuel Oils
3.5 &
check flame length
12-18
1/4"
9-11
Used Crankcase Oil
3.8 &
check flame length
12-18
1/4"
9-11
Used ATF
3.8 &
check flame length
12-18
1/4"
9-11
Used Hydraulic Oil
3.8 &
check flame length
12-18
1/4"
9-11
*If you are burning light viscosity oils such as #2 fuel oil, it may be necessary to install a smaller nozzle. Call
your Clean Burn dealer for more information.
Preparing the Burner for Startup (continued)
ATTENTION:
The settings shown in the charts below are only
initial
adjustments.
Final adjustments must be
done by inspecting the flame length according to the illustrations provided on the following page.
NOTE: The oil pressure is automatically adjusted by the metering pump.
Starting the Burner
1.
Adjust the thermostat setting above room temperature to start the burner.
NOTE:
If the burner refuses to start, review the
Preparing the Burner for Startup
procedure. If,
after repeating this procedure, the burner still refuses to start, check the following system components
for proper functioning:
• Verify that the red wire as shown in the
Burner Wiring Diagram
(Appendix B) is energized
to115VAC.
• Verify that the prime switch (on the control box) is set to RUN (i.e. DOWN position).
2.
Adjusting the Air Regulator:
As soon as the burner starts running, turn the knob on the air regulator clockwise to achieve
proper operating air pressure. Refer to the
Initial Adjustment Charts
.
NOTE:
If the safety reset on the primary control is activated and the burner stops running, see
Section 7 for further instructions on restarting your burner.
(Starting the Burner procedure continued on the next page)
Содержание CB-3500 series
Страница 2: ......
Страница 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Страница 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Страница 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Страница 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Страница 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Страница 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Страница 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Страница 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Страница 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...