Oil Tank Installation Specifications
Ensure that your tank installation adheres to the
following safety guidelines as stated here and in
Section 1
of this manual.
The tank safety label (shown at right) also
summarizes these important specifications for tank
installation and usage. If you do not have a copy of
this label, please contact your Clean Burn dealer for
a copy, which is to be affixed directly to your used
oil supply tank.
• The tank installation must meet all
national and local codes.
Consult your
local authorities for more information as
necessary.
• The tank must be listed to UL 80, UL 142, or
equivalent standard.
• Use a
minimum 250-gallon tank
DO NOT
use a 55-gallon drum as a substitute for an
appropriate tank. The tank must be large
enough to allow water, sludge, etc. to settle
out of the used oil.
• Single wall tanks should have a
manual
shut-off type valve
on the side of the tank
to allow the water, sludge, etc. to be drained
from the bottom of the tank.
• All
unused openings in the tank must be
plugged
or capped off.
• For optimal system functioning, Clean Burn
Recommends inside tank installations as
shown in Figures 4A, 4F, and 4J.
• Some codes require the tank to be
vented to
the outside
of the building using iron or steel
pipe and fittings with an approved vent cap.
• Carefully review the oil tank and pump
installation details as shown in Figures
4A, 4F, and 4J. Pertinent information also
supplied with the metering pump and oil line
installation procedures (following in Sec. 4).
• Ensure that the oil supply tank is
properly
maintained
; refer to Section 9 in this manual
for related procedures.
ATTENTION: For outside tank installations and/or tanks larger than 500 gallons
, contact your
local Clean Burn Distributor for installation recommendations and specifications.
Follow all instructions
for tank installation in
Operator's Manual.
ONLY place these listed substances in
this used-oil supply tank:
• Used crankcase oil
• Used automatic transmission fluid
• Used hydraulic oil
• #2 fuel oil
Do NOT place flammable or corrosive
substances such as gasoline, chlorinated
oils, solvents, paint thinners, or any other
unsafe substances in this used-oil supply tank.
Do NOT weld or allow open flame within
35 feet of this used-oil supply tank.
Tank installation MUST comply with NFPA
30 and 31 Fire Codes, including the following
requirements:
• Tank must be listed to UL 80 or UL 142.
• Tank must be vented to outside.
• Emergency vent or explosion relief must
be installed on tank.
• Inside fill allowed only with funnel including 1/4
turn-to-close fall valve, which must be
closed after filling.
• All other openings must be plugged
• All oil lines must be constructed of copper,
steel, or brass components. Do NOT use
rubber or plastic tubing or piping, or any other
inappropriate material.
42366 Rev. 2
Fire and explosion hazards
To prevent serious injury or death:
WARNING
Содержание CB 140
Страница 2: ......
Страница 8: ...TABLE OF CONTENTS APPENDIX C Furnace Service Record C 1 ...
Страница 40: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 3 20 ...
Страница 72: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 5 6 ...
Страница 80: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 7 4 ...
Страница 96: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 9 10 ...
Страница 104: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 10 8 ...
Страница 116: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 A 12 BLOWER ASSEMBLY CB 1750 2 4 5 6 7 2 8 9 10 1 11 12 1 3 I88954 ...
Страница 128: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 A 24 ...
Страница 142: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 C 2 ...