Operator's Manual: Models CB-1750, CB-2500 & CB-3250
4-23
Stack Safety Switch Specifications
Switching Voltage
24 volts
Switch OPEN Temperature
180 degrees F
Switch Type
L180, normally closed, manual reset
Resetting the Stack Safety Switch
WARNING: BURN HAZARD!
To prevent serious personal injury, be sure to allow ample
time, at least 30 minutes, for the stack, barometric damper, and switch to cool down before
attempting to access and service these components. It is crucial to identify the cause of the stack
obstruction (e.g. heavy snowfall) and correct it
before
resetting the stack safety switch and re-starting
the burner.
DO NOT operate the heating equipment with an obstructed stack
; failure to correct an
obstructed stack may result in fire, explosion, and/or burn hazards causing serious personal injury or
death.
NOTE:
In locations where heavy snowfall occurs, it is critical that the stack remain unobstructed by
snow. For safe heating equipment operation, be sure to keep the area surrounding the stack clear of
snow.
1.
Before resetting the stack safety switch, check the stack to make sure it is clear of any obstructions.
2.
Remove the cover from the stack safety switch, and push the small button in the middle of the switch.
3.
Pushing the stack safety switch reset button will re-establish the thermostat circuit, and the burner will
start (assuming the wall thermostat is calling for heat).
Figure 4P - Stack Safety Switch Wiring Diagram
Understanding the Function of the Stack Safety Switch
The
Stack Safety Switch
monitors the temperature at the barometric damper on the stack and is designed to
detect the obstruction of the free flow of stack gases from the heating equipment and shut down the burner.
Obstruction of the stack results in the “spillage” of stack gases from the barometric damper, which heats up the
switch. The switch then opens, disconnecting the thermostat circuit to the burner, and the burner shuts off.
T
T
F
F
I88965
WALL
THERMOSTAT
OIL
PRIMARY
STACK
SAFETY
SWITCH
(MOUNTED ON
BAROMETRIC DAMPER)
Содержание CB 140
Страница 2: ......
Страница 8: ...TABLE OF CONTENTS APPENDIX C Furnace Service Record C 1 ...
Страница 40: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 3 20 ...
Страница 72: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 5 6 ...
Страница 80: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 7 4 ...
Страница 96: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 9 10 ...
Страница 104: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 10 8 ...
Страница 116: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 A 12 BLOWER ASSEMBLY CB 1750 2 4 5 6 7 2 8 9 10 1 11 12 1 3 I88954 ...
Страница 128: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 A 24 ...
Страница 142: ...Operator s Manual Models CB 1750 CB 2500 CB 3250 C 2 ...