Clayton Steam Generator model EO-100-1M
PAGE 21 / 70
Instruction Manual, doc.nr.: MAN18206 Rev A PSC
6.4
STARTING THE BURNER
•
Start burner. Switch
[S01]
in position burner. After a 10 seconds prepurge time the burner should
ignite. If no flame is detected, the generator will be stopped and a manual reset by switch
[S2]
will be
necessary.
•
After burner is ignited, allow steam generator to come up to operating steam pressure. With the coil
and separator full of water, open separator drain valve
[32]
until first pressure drop shows on
steamtrap pressure gauge
[41].
•
When steam pressure has reached maximum, put control switch
[S01]
in position "HIGH FIRE" and
gradually open steam discharge valve.
•
Check stack for burner smoke. If smoke is noticed regulate the air supply to the burner to eliminate
the smoke and prevent sooting.
•
When the plant has reached full pressure and temperature after initial start, record feed pressure for use
in determining degree of coil restriction.
6.5
AUTOMATIC OPERATION
When steam pressure rises to approximately
XX
bar
)
, the modulating pressure switch
[F22]
will cut burner
capacity to low-fire operation.
On light steam demands or when no steam is required, the steam pressure switch
[F20]
will cut out and stop
the burner when steam pressure rises to working pressure .It will automatically restart the burner when
pressure drops about 1 bar below maximum. The burner will thus cycle between on and off during light
steam demands.
. If the steam demand increases, high-fire operation of the burner will be re-established by means of the
modulating pressure switch
[F22]
when steam pressure drops to +-1 bar below maximum
.
With moderate to
heave steam demands, the burner will cycle between high and low-fire operation, or operate on high fire
continuously, depending on the steam demand
During on/off or low-fire/high-fire operation of the pump will operate by means of the 2 speed motor
.
6.6
SHUTTING DOWN THE GENERATOR
PURPOSE AND SCOPE
The purpose of conserving generators, exhaust gas boilers or any other installation is to protect the
installation against in- and outside corrosion and/or freezing during periods of shutdown.
Protection of generators, exhaust gas boilers or others parts during fabrication and/or storage,
(that is before
they are incorporated in an installation)
is described in a Clayton procedure
BASE AND REFERENCE DOCUMENTS
-- Clayton installation manual
-- Clayton instruction manual
WARNING :
Start the burner only when the water pump has been properly deaerated and
when the generator is completely filled with water
NOTE :
Pressures given in the following text are typical for a unit adjusted for a maximum
operating pressure of 10 bar. The pressure ranges given in parenthesis are the values that have to be
substracted from the maximum operation pressure if the unit is adjusted for other pressures.