12. Infrared Configuration Unit (ICU) guide

Entering configuration mode

Point the ICU towards the 

Easyflush

EVO

 sensor 

and press the configuration   button, LEDs will 

flash 

amber

. Activation is most effective when the 

configuration button is held down as the ICU is 

brought close to the sensor.
It can take up to 3 seconds for the product to 

sense the ICU. The 

Easyflush

EVO

 will return to 

normal operation if there are no button presses 

for 30 seconds.

Configuring sensor range

Point the ICU at the 

Easyflush

EVO

 sensor and 

press the 

1

   sensor range button (the sensor 

blinks 

green

).

Decrease or increase the sensor range by  

pressing the and buttons respectively. 
The sensor blinks red when the min or max  

value is reached.

Press the   button to check the sensor range 
setting - the sensor displays the current setting by 
flashing 

green

; see table.

Save setting and exit ICU configuration mode by 
pressing

the button.

Exit without saving by pressing the

button.

Activates cleaning mode
Activates ICU configuration mode
Decreases setting
Increases setting
Checks the setting being altered
Saves changes and exits ICU configuration mode
Quits ICU configuration mode without saving changes
Configures sensor range
Configures full/part flush time
Configures cistern refill time
Toggles Wave function ON/OFF (Walkaway ONLY)
12-hour hygiene cycle activation
Dual flush activation
Autorange setting of sensor range
No function
Switch Wave & Walkaway variants & resets to default 

factory settings

5

Button descriptions

1

4

2

3

8

7

6

NOTE:

 Not supplied but available from Cistermiser or any major plumbing merchant.

9

For Wave version

Number of flashes

1

2

3

4

5

Range (cm approx)

5

10

15

20 25

For Walkaway version

Number of flashes

1

2

3

4

5

Range (cm approx)

45

50

55

60 65

Configuring Full/Part flush time

Point the ICU at the 

Easyflush

EVO

 sensor and press 

the 

2

   

flush time button (the sensor blinks 

green

).

Decrease or increase the flush time by pressing the

and buttons respectively. The sensor blinks 

red

 when the min or max value is reached.

Press the   button to check the flush time setting 

- the sensor displays the current setting by flashing 

green

; see table.

Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

Configuring refill time

Point the ICU at the 

Easyflush

EVO

 sensor and press 

the 

3

   refill time button (the sensor blinks 

green

).

Decrease or increase the refill time by pressing the

and buttons respectively. The sensor blinks 

red

 when the min or max value is reached.

Press the   button to check the refill time  

setting - the sensor displays the current setting by 

flashing 

green

; see table.

Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

Hand wave flushing (walkaway 

mode only) activation and 

de-activation

Point the ICU at the 

Easyflush

EVO

 sensor and 

press the

 

4

 

 (the sensor blinks 

green

). By 

default the hand wave function is on. 
Pressing the and button switches the hand 

wave function on or off respectively. 
Press the   button to check the setting - the 

sensor flashes 

green

 once if function is off or 

twice if it is on.
Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

12 hour hygiene flush activation 

and de-activation

Point the ICU at the 

Easyflush

EVO

 sensor and press 

the hygiene cycle button (the sensor blinks 

green

).

Pressing the and buttons switches the hygiene 

flush function on or off respectively. 
Press the   button to check the setting - the sensor 

flashes 

green

 once if function is off or twice if it is on.

Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

Dual flush activation and 

de-activation

Point the ICU at the 

Easyflush

EVO

 sensor and press 

the 

6

    (the sensor blinks 

green

).

Pressing the and buttons switches the  

dual flush function on or off respectively. Press the 

 button to check the setting - the sensor flashes 

green

 once if function is off or twice if it is on.

Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

Configuring sensor range using

the autorange function

If the cubicle door is opposite the sensor, ensure that 

the cubicle door is closed or ajar, but not fully open.
Point the ICU at the 

Easyflush

EVO

 sensor and press 

the

 

7

   

button.

Immediately stand clear of the sensor. Sensor 

blinks 

green

 for 5 seconds, then a steady 

green

 

when setting complete. The sensor measures the 

background reflections and sets the sensor range 

to an appropriate setting.
Save setting and exit ICU configuration mode by 

pressing the

button.

Exit without saving by pressing the

button.

Only possible when configured as Walkaway.

Wave/walkaway conversion

Point the ICU at the sensor and press the 

9

 

  

button (the sensor blinks 

green

).

Pressing the and button switches the function 

to Wave and Walkaway respectively. Press the OK 

button to check the setting - the sensor flashes 

green

 once if wave or twice if walkaway.

Save setting and exit ICU configuration by pressing 

the

button.

Exit without saving by pressing the

button.

Number of flashes

1

2

3

4

5

Full flush time (sec)

3

4

8

Part flush time (sec) 1½

2

2¾ 3¾ 5½

Number of flashes 1

2

3

4

5

6

7

Refill time (sec)

0 20 40 60 80 100 120

Содержание Easyflush EVO 1.5

Страница 1: ...EasyflushEVO EVO 1 5 EVO 2 EVO CISTERN SUSTAINABILITY A W A R D S 2 0 2 2...

Страница 2: ...tem washer with boss 5 Outlet nut 6 Cap seal 7 Cap washer 8 Cap nut 9 Flush valve 10 IR Sensor unit 11 Sensor gasket 12 Sensor nut 13 Clamp plate 14 Screw packer 15 IR activation label walk wave 16 Ma...

Страница 3: ...d water supply The flush is activated by the IR Sensor unit This can be configured to flush on a wave default or flush when the user walks away Wave default Walk Away Memory Flush If a flush is activa...

Страница 4: ...f valve EasyflushEVO Flush Valve water level Unlock To adjust height of EasyflushEVO Flushing Valve rotate upper body clockwise to release Adjust Lift or lower upper body to adjust height Lock Rotate...

Страница 5: ...ll Medium thickness wall Thick wall 6 Power Connections Isolate mains power supply before proceeding Mains wiring should be undertaken by a competent person Battery Case Open case and fit 4 x AA LR 6...

Страница 6: ...nce per second Memory flush refilling Alternating 3 green LEDs rising Faulty wiring 2 red LEDs single flash once per second Low battery power fault 1 red LED single flash once per second NOTE For chem...

Страница 7: ...DC regulated from mains adaptor 1A fused spur required Normal battery life 27 000 cycles Cleaning Clean with soap and water only Lens care Infrared lens can be polished with a soft cloth Electronic sp...

Страница 8: ...onds until constant triple green LEDs show Sensor distance is now set A B C Wave sensing range adjustment when Wave variant is selected Refill duration adjustment Wait for 4 x triple red LEDs to enter...

Страница 9: ...ively The sensor blinks red when the min or max value is reached Press the button to check the refill time setting the sensor displays the current setting by flashing green see table Save setting and...

Страница 10: ...e float accordingly If the float is set too high water will continuously flow into the cistern and out of the overflow Cistermiser product warranty and extended warranty Cistermiser products are guara...

Страница 11: ...or installation refer to advanced settings guide section 11 10 Test operation a Wave Place hand within 10cm of sensor for 1 second valve will part flush and the sensor will flash the single green LED...

Страница 12: ...22 cistermiser co uk Have a question Call our customer support team on 0118 969 1611 Have a question Call our customer support team on 0118 969 1611 cistermiser co uk 23 Notes...

Страница 13: ...commercial and industrial applications worldwide keraflo co uk Combimate is a domestic limescale prevention device that prevents limescale build up and soft water corrosion in combination boilers and...

Отзывы: