12. Infrared Configuration Unit (ICU) guide
Entering configuration mode
Point the ICU towards the
Easyflush
EVO
sensor
and press the configuration button, LEDs will
flash
amber
. Activation is most effective when the
configuration button is held down as the ICU is
brought close to the sensor.
It can take up to 3 seconds for the product to
sense the ICU. The
Easyflush
EVO
will return to
normal operation if there are no button presses
for 30 seconds.
Configuring sensor range
Point the ICU at the
Easyflush
EVO
sensor and
press the
1
sensor range button (the sensor
blinks
green
).
Decrease or increase the sensor range by
pressing the and buttons respectively.
The sensor blinks red when the min or max
value is reached.
Press the button to check the sensor range
setting - the sensor displays the current setting by
flashing
green
; see table.
Save setting and exit ICU configuration mode by
pressing
the button.
Exit without saving by pressing the
button.
Activates cleaning mode
Activates ICU configuration mode
Decreases setting
Increases setting
Checks the setting being altered
Saves changes and exits ICU configuration mode
Quits ICU configuration mode without saving changes
Configures sensor range
Configures full/part flush time
Configures cistern refill time
Toggles Wave function ON/OFF (Walkaway ONLY)
12-hour hygiene cycle activation
Dual flush activation
Autorange setting of sensor range
No function
Switch Wave & Walkaway variants & resets to default
factory settings
5
Button descriptions
1
4
2
3
8
7
6
NOTE:
Not supplied but available from Cistermiser or any major plumbing merchant.
9
For Wave version
Number of flashes
1
2
3
4
5
Range (cm approx)
5
10
15
20 25
For Walkaway version
Number of flashes
1
2
3
4
5
Range (cm approx)
45
50
55
60 65
Configuring Full/Part flush time
Point the ICU at the
Easyflush
EVO
sensor and press
the
2
flush time button (the sensor blinks
green
).
Decrease or increase the flush time by pressing the
and buttons respectively. The sensor blinks
red
when the min or max value is reached.
Press the button to check the flush time setting
- the sensor displays the current setting by flashing
green
; see table.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Configuring refill time
Point the ICU at the
Easyflush
EVO
sensor and press
the
3
refill time button (the sensor blinks
green
).
Decrease or increase the refill time by pressing the
and buttons respectively. The sensor blinks
red
when the min or max value is reached.
Press the button to check the refill time
setting - the sensor displays the current setting by
flashing
green
; see table.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Hand wave flushing (walkaway
mode only) activation and
de-activation
Point the ICU at the
Easyflush
EVO
sensor and
press the
4
(the sensor blinks
green
). By
default the hand wave function is on.
Pressing the and button switches the hand
wave function on or off respectively.
Press the button to check the setting - the
sensor flashes
green
once if function is off or
twice if it is on.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
12 hour hygiene flush activation
and de-activation
Point the ICU at the
Easyflush
EVO
sensor and press
the hygiene cycle button (the sensor blinks
green
).
Pressing the and buttons switches the hygiene
flush function on or off respectively.
Press the button to check the setting - the sensor
flashes
green
once if function is off or twice if it is on.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Dual flush activation and
de-activation
Point the ICU at the
Easyflush
EVO
sensor and press
the
6
(the sensor blinks
green
).
Pressing the and buttons switches the
dual flush function on or off respectively. Press the
button to check the setting - the sensor flashes
green
once if function is off or twice if it is on.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Configuring sensor range using
the autorange function
If the cubicle door is opposite the sensor, ensure that
the cubicle door is closed or ajar, but not fully open.
Point the ICU at the
Easyflush
EVO
sensor and press
the
7
button.
Immediately stand clear of the sensor. Sensor
blinks
green
for 5 seconds, then a steady
green
when setting complete. The sensor measures the
background reflections and sets the sensor range
to an appropriate setting.
Save setting and exit ICU configuration mode by
pressing the
button.
Exit without saving by pressing the
button.
Only possible when configured as Walkaway.
Wave/walkaway conversion
Point the ICU at the sensor and press the
9
button (the sensor blinks
green
).
Pressing the and button switches the function
to Wave and Walkaway respectively. Press the OK
button to check the setting - the sensor flashes
green
once if wave or twice if walkaway.
Save setting and exit ICU configuration by pressing
the
button.
Exit without saving by pressing the
button.
Number of flashes
1
2
3
4
5
Full flush time (sec)
2¼
3
4
5½
8
Part flush time (sec) 1½
2
2¾ 3¾ 5½
Number of flashes 1
2
3
4
5
6
7
Refill time (sec)
0 20 40 60 80 100 120