7. Testing and Commissioning
Ensure flush valve and fill valve are set to the same height level (see page 6) so the water level is at the
mark on the Flush valve.
Ensure cistern is level and check for leaks.
Activate flush via sensor or manual override to verify operation.
Sensor LED Glossary
Full flush via Wave or
Walkaway - 2
green
LEDs
single flash once per second
Scratched lens/blocked sensor
- 3
red
LEDs single flash once
per second
Part Flush via Wave or
Walkaway - 1
green
LED
single flash once per second
Servo motor obstruction
(Call Cistermiser for advice) -
2
red
LEDs single flash once
per second
Memory flush/refilling
Alternating, 3
green
LEDs
rising...
Faulty wiring - 2
red
LEDs
single flash once per second
Low battery/power fault - 1
red
LED single flash once per
second
NOTE:
For chemical water treatment.
If the water system has been treated with chemical dosing, ensure the
system is thoroughly flushed before fitting any Cistermiser products. Concentrated chemicals in dead
legs can damage the product and result in failure. If the water is treated with Chlorine Dioxide (ClO2),
ensure concentration levels are maintained below 5ppm.
Lift override lever to
activate flush
Ensure lever is returned
to lower reset position
8. Maintenance
Fill valve (supplied with EVO CISTERN only): Periodically rinse the inlet filter and valve diaphragm. If the
diaphragm is damaged contact Cistermiser for a replacement.
You may rinse the filter or the membrane to maintain your fill valve.
If the membrane is damaged, you need to replace it.
*
Amber
LED = Configuration