Dryer Installation with Separate Exhaust (Preferred) (Illustration)
DRYER INSTALLATION WITH SEPARATE EXHAUST
(PREFERRED)
For Exhaust Duct less than 14 feet and 2 elbows equivalent and
less than 0.3 inches static pressure.
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or make-
up air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-up air opening from outside the building may enter the
enclosure from the top or side walls. Area of opening should
be equal to 4-6 times the sum of dryer duct areas. Provide 1
sq. ft. for each 6 in. diameter; 2 sq. ft. for each 8 in. diameter;
and 4 sq. ft. for each 12 in. diameter.
2. Enclosure (plenum) with service door. This separates the
dryer air from the room comfort air. If dryers use room air
instead of outside air, the heat loss can be another 25 BTU/HR
for each cubic foot per minute (CFM) used.
EXAMPLE:
A 110 lb. dryer with 2000 CFM = heat loss of
50,000 BTU/HR.
3. Zero inches clearance to combustible material allowed on
sides and at points within 4 inches of front on top.
4. Heat loss into laundry room from dryer fronts
only
is about 60
BTU/HR per square foot.
DRYER INSTALLATION
WITH SEPARATE
EXHAUST (PREFERRED)
Содержание L28FD30
Страница 1: ...R1 2 07...
Страница 10: ...Page 10 110 lb Gas Fired Dryer Models L44CD42G and L44KD42G Illustration...
Страница 11: ...Page 11 110 lb Steam Heated Dryer Models L44CD42S and L44KD42S Illustration...
Страница 12: ...Page 12 110 lb Electric Dryer Model L44CD42E Illustration...
Страница 13: ...Page 13 110 lb Gas Fired Dryer Models L44FD42G and L44RD42G Illustration ENERGY SAVERMODEL...
Страница 19: ...Page 19 Gas Loop Piping and Gas Supply Piping System Illustrations...
Страница 23: ...Page 23 Steam Piping Installation Illustration...
Страница 25: ...Page 25 10 16cm Dryer Installation with Multiple Exhaust Illustration...
Страница 31: ...Page 31 Two Timer Models Figures 1 2 and 3 Illustrations...