Page 21
1. The installation must conform to
local codes
or in absence of
local codes, with the
National Fuel Gas Code as ANSI
Z223.1—Latest Edition
.
2. Check with utilities for proper gas pressure and gas supply
line.
3. Check for altitude elevation of the dryer.
4. The dryer and its individual shut-off valve must be
disconnected from the gas supply piping system at test
pressures in excess of 1/2 PSIG.
5. The dryer must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system, at test
pressures equal to or less than 1/2 PSIG.
NATURAL GAS ONLY
Check the gas pressure inlet supply to the dryer, 11 inches WC
Pressure maximum. Check the manifold pressure, 3.5 inches
WC Pressure inside the dryer.
CAUTION
Low gas pressure and intermittent gas will cause gas ignition
problems and inadequate drying of the clothes load.
Gas Piping Installation
GAS PIPING
INSTALLATION
Содержание L28FD30
Страница 1: ...R1 2 07...
Страница 10: ...Page 10 110 lb Gas Fired Dryer Models L44CD42G and L44KD42G Illustration...
Страница 11: ...Page 11 110 lb Steam Heated Dryer Models L44CD42S and L44KD42S Illustration...
Страница 12: ...Page 12 110 lb Electric Dryer Model L44CD42E Illustration...
Страница 13: ...Page 13 110 lb Gas Fired Dryer Models L44FD42G and L44RD42G Illustration ENERGY SAVERMODEL...
Страница 19: ...Page 19 Gas Loop Piping and Gas Supply Piping System Illustrations...
Страница 23: ...Page 23 Steam Piping Installation Illustration...
Страница 25: ...Page 25 10 16cm Dryer Installation with Multiple Exhaust Illustration...
Страница 31: ...Page 31 Two Timer Models Figures 1 2 and 3 Illustrations...