Step 3
Attach the grounding cable to the grounding point on the side of the chassis.
a) Position the ground lug.
b) Align the terminal holes in the ground lug with the terminal holes in the side of the chassis.
c) Using a #2 Phillips screwdriver, insert and tighten two M5 x 10mm pan-head screws to secure the grounding cable
to the side of the chassis.
Screw down ground cable to secure it
to the side-mount ground point
2
Assembled ground cable with lug
positioned on chassis ground point
1
Connecting Rear-Mount Earth Ground
Connecting the chassis to facility earth ground is supported through the chassis ground bracket, which installed
at the side of the bottom set of PSUs.
The facility ground cable must be terminated with the ground lug provided by Cisco, or an equivalent. For
more information, see "Ground Lug" in
Earth Ground Considerations, on page 21
.
Use this procedure to connect the chassis to earth ground.
Before you begin
This procedure assumes that you have already attached the bottom cable management bracket with the
grounding bracket included. For information, see
Installing the Ground Bracket and Bottom Cable Management
.
Step 1
Verify that the ground bracket is correctly installed. If not, install it now. See
Installing the Ground Bracket and Bottom
Cable Management Arms, on page 39
.
Cisco UCS X9508 Server Chassis Installation Guide
48
Installation
Connecting Rear-Mount Earth Ground
Содержание UCS X9508
Страница 6: ...Cisco UCS X9508 Server Chassis Installation Guide vi Contents ...
Страница 26: ...Cisco UCS X9508 Server Chassis Installation Guide 18 Overview Interpreting LEDs ...
Страница 31: ...Cisco UCS X9508 Server Chassis Installation Guide 23 Installation Handling the Chassis ...
Страница 64: ...Cisco UCS X9508 Server Chassis Installation Guide 56 Installation Repacking the Chassis ...
Страница 124: ...Cisco UCS X9508 Server Chassis Installation Guide 116 Technical Specifications Switzerland ...