Figure 21 AC/DC Power Input Terminal Block Wire Connections to a DC Source
Warning:
An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that
no exposed portion of the DC-input power source wire extends from the power and relay connector.
Statement 122
7.
Insert the twisted-pair wire leads into the terminal block line and neutral connections.
8.
Insert the wire (labeled number 1 in
) lead into the neutral wire connection and the wire (labeled
) lead into the line wire connection.
Ensure that only wire
with
insulation
extends from the connectors. See
9.
Tighten the line and neutral terminal block screws to 8 in.-lb torque.
note:
Do not exceed 10 in-lb torque.
10.
Connect the red wire to the positive pole of the DC power source, and connect the black wire to the return pole.
Ensure that each pole has a current-limiting-type fuse rated to at least 600 VAC/DC (such as the KLKD Midget fuse).
Wiring the DC Power Source
Read these cautions and warnings before wiring the switch the DC power source.
Caution:
This product is intended to be supplied by a Listed Class 2 power source marked with Class 2 and rated from
9.6V to 60VDC, 2.1A.
Warning:
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Statement 1022
Warning:
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than: 3A.
Statement 1005
Warning:
Installation of the equipment must comply with local and national electrical codes.
Statement 1074
Warning:
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
1
Earth ground wire connection
3
Positive DC connection
2
Return wire connection (to DC return)
347819
3
2
1