Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-09
Chapter 8 Cisco ASR 1002 Router Overview and Installation
Cisco ASR 1002 Router Power Supplies
Figure 8-27
Cisco ASR 1002 Router –48 VDC Power Supply Terminal Block Cable Connections
Step 3
Using a wire stripper, strip approximately 0.55 inch (14 mm) from the negative, positive, and ground
lead.
Step 4
Insert the stripped end of the ground lead all the way into the ground lead receptacle on the –48 VDC
input power supply, and tighten the receptacle screw using a 3.5mm flat-blade screwdriver to a torque of
0.5 to 0.6Nm.
Step 5
Insert the stripped end of the positive lead all the way into the positive lead receptacle and tighten the
receptacle screw using the same 3.5mm flat-blade screwdriver. Repeat this step for the negative lead.
Note
Make sure the entire stripped end of each lead is inserted all the way into its receptacle. If any
exposed wire at the stripped end of a lead is visible after inserting the lead into its receptacle,
remove the lead from the receptacle, use the wire stripper to cut the stripped end of the lead, and
repeat Step 3 through Step 5.
Step 6
After tightening the receptacle screw for the ground, positive, and negative –48 VDC-input leads, use a
cable tie to secure the three leads to the power supply faceplate, as shown in
Figure 8-27
. When securing
the ground, positive, and negative –48 VDC-input leads to the power supply faceplate, leave a small
service loop in the ground lead to ensure that the ground lead is the last lead to disconnect from the power
supply if a great deal of strain is placed on all three leads as shown in
Figure 8-27
.
Caution
Make certain that the ground lead wire has a service loop before you tie wrap the lead wires to prevent
the ground from being disconnected.
Step 7
Connect the ground, positive, and negative leads to the power source.
1
Ground lead with service loop and tie-wrap
3
Negative lead
2
Positive lead
4
–48 VDC power supply Standby switch
OUTPUT INPUT
FAIL
OK
OK
FAN
-48V/-60V 16
A
This unit might h
ave more than
one power supp
ly connection.
All connections m
ust be removed
to de-energize
the unit.
3
1
2
280290
4