Rear rack-mount brackets (2)
◦
Slider rails (2)
◦
M4 x 0.7 x 8-mm Phillips countersink screws (12)
•
The rack is installed and secured to its location.
Step 1
Install two front-mount brackets to the switch as follows:
a) Determine which end of the chassis is to be located in the cold aisle as follows:
•
If the switch has port-side intake modules (fan modules with burgundy coloring), position the switch so that its
ports will be in the cold aisle.
•
If the switch has port-side exhaust modules (fan modules with blue coloring), position the switch so that its fan
and power supply modules will be in the cold aisle.
If the power supply modules have white coloring, look at the fan modules to determine the airflow direction
for the switch.
Note
b) Position a front-mount bracket so that four of its screw holes are aligned to the screw holes on the side of the chassis.
You can align any four of the holes in the front rack-mount bracket to four of the six screw holes on the side
of the chassis (see the two ways to mount these brackets on a typical chassis, in following figure). The holes
that you use depend on the requirements of your rack and the amount of clearance required for interface
cables (3 inches [7.6 mm] minimum) and module handles (1 inch [2.5 mm] minimum).
Note
Cisco Nexus 93180YC-EX ACI Mode Hardware Installation Guide
17
Installing the Switch Chassis
Installing the Switch
Содержание 9300-EX
Страница 6: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide vi Contents ...
Страница 14: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 4 Overview Overview ...
Страница 22: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 12 Preparing the Site Clearance Requirements ...
Страница 67: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 57 LEDs Power Supply LEDs ...
Страница 68: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 58 LEDs Power Supply LEDs ...