For the power cables to use with the power supplies, see
Power Cable Specifications, on page 50
.
Note
Airflow Requirements
The switch is designed to be positioned with its ports in either the front or the rear of the rack depending on
your cabling and maintenance requirements. Depending on which side of the switch faces the cold aisle, you
must have fan and power supply modules that move the coolant air from the cold aisle to the hot aisle in one
of the following ways:
•
Port-side exhaust airflow
—
Coolant air enters the chassis through the fan and power supply modules in
the cold aisle and exhausts through the port end of the chassis in the hot aisle.
•
Port-side intake airflow
—
Coolant air enters the chassis through the port end in the cold aisle and exhausts
through the fan and power supply modules in the hot aisle.
•
Dual-direction airflow
—
Airflow direction is determined by the airflow direction of the installed fan
modules.
You can identify the airflow direction of each fan and power supply module by its coloring as follows:
•
Blue coloring indicates port-side exhaust airflow.
•
Burgundy coloring indicates port-side intake airflow.
•
White coloring on HVAC/HVDC power supplies indicates dual-direction airflow.
•
Gray coloring on DC power supplies indicates port-side exhaust airflow.
•
Green coloring on DC power supplies indicates port-side intake airflow.
To prevent the switch from overheating and shutting down, you must position the air intake for the switch
in a cold aisle, and all of the fan and power supply modules must have the same direction of airflow (even
if their coloring is different). If you must change the airflow direction for the switch, you must shutdown
the switch before changing the modules.
Note
Rack and Cabinet Requirements
You can install the following types of racks or cabinets for your switch:
•
Standard perforated cabinets
•
Solid-walled cabinets with a roof fan tray (bottom-to-top cooling)
•
Standard open four-post Telco racks
Work with your cabinet vendors to determine which of their cabinets meet the following requirements or see
the Cisco Technical Assistance Center (TAC) for recommendations:
Cisco Nexus 93180YC-EX ACI Mode Hardware Installation Guide
9
Preparing the Site
Airflow Requirements
Содержание 9300-EX
Страница 6: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide vi Contents ...
Страница 14: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 4 Overview Overview ...
Страница 22: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 12 Preparing the Site Clearance Requirements ...
Страница 67: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 57 LEDs Power Supply LEDs ...
Страница 68: ...Cisco Nexus 93180YC EX ACI Mode Hardware Installation Guide 58 LEDs Power Supply LEDs ...