A-77
Catalyst 6500 Series Switches Installation Guide
OL-5781-08
Appendix A Power Supply Specifications
Power Supply Redundancy
Note
In systems that are equipped with two power supplies, if one power supply fails and the other power
supply cannot fully power all of the installed modules, system power management will shut down
devices in the following order:
•
Power over Ethernet (PoE) devices— The system will power down PoE devices in descending order,
starting with the highest numbered port on the module in the highest numbered slot.
•
Modules—If additional power savings are needed, the system will power down modules in
descending order, starting with the highest numbered slot. Slots containing supervisor engines or
Switch Fabric Modules are bypassed and are not powered down.
This shut down order is fixed and cannot be changed.
You can change the configuration of the power supplies to redundant or combined at any time. If you
switch from a redundant to a combined configuration, both power supplies are enabled (even a power
supply that was disabled because it was of a lower wattage than the other power supply). If you change
from a combined to a redundant configuration, both power supplies are initially enabled, and if they are
of the same wattage, they remain enabled. If they are of different wattage, a syslog message displays and
the lower wattage supply is disabled.
For additional information about the power management feature and individual module power
consumption, refer to your software configuration guide.
Содержание 6500 - Catalyst Series 10 Gigabit EN Interface Module Expansion
Страница 4: ......
Страница 18: ...xviii Catalyst 6500 Series Switches Installation Guide OL 5781 08 Preface Conventions ...
Страница 444: ...D 16 Catalyst 6500 Series Switches Installation Guide OL 5781 08 Appendix D Chassis and Module Power and Heat Values ...
Страница 452: ...E 8 Catalyst 6500 Series Switches Installation Guide OL 5781 08 Appendix E Troubleshooting Contacting Customer Service ...