4�4�- KEYBOARD FUNCTIONS
The device has 7 keys,
.
1�- Keys accessible with sealed cover and tool
RESET
, Starts the device after a trip.
TEST
, Carries out a trip to check the proper operation of the relay.
PROG/PAG
, dual-function key:
∙
A short press displays earth leakage or overcurrent reclosings.
∙
A long press opens the device programming menu.
2�-
Keys accessible with cover open
Keys with dual function. With a long press, the device is entered to set the values. With a short press,
the option within a series of values defined in the device is selected.
SENSITIVITY (I
Δn
)
, It allows to choose between the values of 30, 100, 300, 500 mA , 1 and 3 A
Specifying the expanded scale in the settings adds 5, 10 and 30 A to the list of values above.
DELAY (td)
, It allows to choose between the values of 20, 100, 200, 300, 400, 500, 750 ms
and 1 s.
Specifying the expanded scale in the settings adds 5, 10 and 30 A to the list of values above.
This key can also be used to navigate inside the programming menu.
3�- Keys accessible with cover open and tool
Flush buttons.
SAFETY (Std/+)
, used to configure the polarity of the contacts on the interlock relay (Termi-
nals 7, 8 and 9).
●
With normal safety (Std) the relay is activated with a fault, the status is NO.
●
With positive safety (+) the relay is activated on supplying the device and is deactivated with
the fault, the status is NC.
REC
, used to enable or disable the overcurrent and earth leakage reclosing.
When in the reclosings screen, it is used to change the number of maximum overcurrent and
earth leakage reclosings.
Содержание RGU-10 MT
Страница 1: ...INSTRUCTION MANUAL Electronic earth leakage protection relay RGU 10 MT Serie M98228501 03 21A...
Страница 2: ...2 RGU 10 MT Instruction Manual...
Страница 38: ...38 RGU 10 MT Instruction Manual 12 CE CERTIFICATE...
Страница 39: ...39 Instruction Manual RGU 10 MT...
Страница 40: ...40 RGU 10 MT Instruction Manual...
Страница 41: ...41 Instruction Manual RGU 10 MT...