19
Instruction Manual
RGU-10 MT
4�5�- DISPLAY
The device has a backlit display with
green
or
red
light, depending on the state of the device.
The background to the screen in normal mode is
green
. The parameters required for earth leakage
protection, sensitivity and delay in its associated units are displayed. It also displays the current leak-
age current.
If the device trips through any event, the screen’s background changes to
red
and the reason for the
trip is displayed.
Figure 12: Display RGU-10 MT�
Display messages by device trip,
.
Table 6: Display messages by device trip�
Message
Cause of trip
TESt
Test
EXT
Remote signa
l
ON/OFF
REM
RS-485 communications
DIF / Valor
Differential
MAG
Circuit breaker
Other display messages,
Table 7: Other display messages�
Message
Description
SAVE
Validate configuration values
EXIT
Exits programming mode
ERRt
Poor toroid connection
OVR
Current leakage reading off scale
Содержание RGU-10 MT
Страница 1: ...INSTRUCTION MANUAL Electronic earth leakage protection relay RGU 10 MT Serie M98228501 03 21A...
Страница 2: ...2 RGU 10 MT Instruction Manual...
Страница 38: ...38 RGU 10 MT Instruction Manual 12 CE CERTIFICATE...
Страница 39: ...39 Instruction Manual RGU 10 MT...
Страница 40: ...40 RGU 10 MT Instruction Manual...
Страница 41: ...41 Instruction Manual RGU 10 MT...