4�3- COMMUNICATIONS
ReadWatt
has two communications ports, RS-232 and RS-485. Both ports can be used simultaneously.
The transmission speed, Baudrate, is the same for both ports and can be configured.
4�3�1�- MODBUS PROTOCOL
The
MODBUS
protocol is a communication standard in the industry that enables the network
connection of multiple devices, where there is a master and multiple slaves. Within the
MODBUS
protocol
ReadWatt
uses the RTU (Remote Terminal Unit) mode.
In RTU mode the start and end of the message is detected with silences with a minimum of 3.5
characters and the 16-bit CRC error detection method is used.
The
MODBUS
functions implemented in the device are:
Functions 03 and 04
. Reading of registers.
Function 10
. Writing of multiple registers.
4�3�2�- READ COMMANDS
ReadWatt
supports the integer type read functions:
0x03
and
0x04
.
The device's
MODBUS
variables are specified in
.
Example:
Reading of the device's serial number with peripheral number 01.
We will send the following
MODBUS
frame:
Address
Function
Initial
Register
Register no�
CRC
01
04
0060
0002
CRC
The device will respond to us with the next frame:
Address
Function
No� of bytes
Serial no�
CRC
01
04
04
XXXX XXXX
CRC
Note:
The values are shown in hexadecimal.
The number of requested logs must be the same as the size of the variable requested.
It is possible to read several consecutive addresses, if the request meets the correct format.
14
ReadWatt
Instruction Manual
Содержание ReadWatt
Страница 1: ...INSTRUCTION MANUAL M018B01 03 22A Impulse sensor ReadWatt...
Страница 2: ...2 ReadWatt Instruction Manual...
Страница 19: ...32 15 25 6 Figure 10 ReadWatt dimensions 19 Instruction Manual ReadWatt...
Страница 21: ...8 CE CERTIFICATE 21 Instruction Manual ReadWatt...
Страница 22: ...22 ReadWatt Instruction Manual...
Страница 23: ...23 Instruction Manual ReadWatt...